3. Controls and Adjustments

Dip switches are factory set. Failure to maintain factory settings may adversely
affect performance and warranty coverage. For more information, contact
Hoshizaki Technical Support at 1-800-233-1940.

a) Default Dip Switch Settings

The dip switches are factory set to the following positions:
S4 Dip Switch No.
KMS-822MLH
S5 Dip Switch (Do Not Adjust)
S5 Dip Switch No. 1
KMS-822MLH
b) Harvest Timer (S4 dip switch 1 & 2)
The harvest timer starts when the thermistor reads 48°F (9°C) at the evaporator outlet
and the control board reads the thermistor's 3.9 kΩ signal. The harvest timer is factory
set, and generally no adjustment is required. However, a setting longer than the factory
setting may be advised in cases where harvest needs to be prolonged for extra cleaning.
Before changing this setting, contact your local Hoshizaki distributor or Hoshizaki
Technical Support for recommendations. Keep in mind that setting the harvest timer to a
longer setting decreases 24-hour production.
The pump-out timer (S4 dip switch 3 & 4) acts in place of the harvest timer during cycles
with a pump-out. For details, see "II.C.3.c) Pump-Out Timer (S4 dip switch 3 & 4)."
S4 Dip Switch
1
2
3
4
OFF OFF OFF ON ON ON ON OFF OFF ON
2
3
4
5
OFF OFF OFF OFF OFF
Pump-Out Frequency Control (5 & 6)
Pump-Out Timer (3 & 4)
(Do not adjust out of factory setting)
Harvest Timer (1 & 2)
S4 Dip Switch Setting
No. 1
OFF
ON
OFF
ON
CAUTION
5
6
7
8
9
Freeze Timer (9 & 10)
Factory Use (8)
Harvest Pump Timer (7)
(Do not adjust)
Time
(seconds)
No. 2
OFF
60
OFF
90
ON
120
ON
180
17
10