TYPICAL FIXED ORIFICE INSTALLATION
PROCEDURE
1. Installed the provided RFC orifice that was supplied
with the outdoor unit as illustrated in figure 18.
2. Ensure that the fixed orifice supplied with the outdoor
unit is installed with the nylon seat pointing toward the
liquid line orifice housing.
3. Apply a small amount of refrigerant oil on the Teflon
ring and insert securely into the liquid line orifice
housing.
4. Attach the liquid line assembly to the liquid line orifice
housing. Finger tighten and use an appropriately sized
wrench to turn an additional 1/2 turn clockwise as
illustrated in figure 17, or 20 ft−lb.
5. Place the supplied fixed orifice sticker on the indoor
cabinet after installation.
LIQUID LINE ASSEMBLY
WITH BRASS NUT
(Uncased Coil Shown)
Figure 18. Typical Fixed Orifice Installation
See the 13ACD Engineering Handbook for approved TXV
indoor/outdoor
unit
information. Table 4 lists both the Lennox catalog and part
numbers for the TXV kit required for each unit model.
Figure 19 illustrates the kit components and quantities.
Table 3. Indoor Fixed Orifice Kits
Catalog
Number
Model
018
10W95
024
98M12
030
11W00
036
98M78
042
10W86
048
98M14
060
98M15
Use the Lennox catalog number to order a new or replacement fixed
orifice kit.
The kit includes:
S
1
Fixed orifice
505366M 01/08
LIQUID LINE ORIFICE HOUSING
FIXED
ORIFICE
TEFLON
WASHER
LIQUID
LINE
match−ups
and
application
Part Number
Drill Size
100484−07
0.055
100484−12
0.062
100484−16
0.067
100484−24
0.076
100484−28
0.080
100484−36
0.089
100484−45
0.099
S
1
Fixed orifice extractor
S
1
Teflon ring
S
1
Fixed orifice sticker
Figure 19. Fixed Orifice Kit Components
TYPICAL TXV INSTALLATION PROCEDURE
The TXV unit can be installed internal or external to the
indoor coil. In applications where an uncased coil is being
installed in a field−provided plenum, install the TXV in a
manner that will provide access for field servicing of the
TXV. Refer to Figure 20 for reference during installation of
TXV unit.
1. Install one of the provided Teflon rings around the
stubbed end of the TXV and lightly lubricate the
connector threads and expose surface of the Teflon
ring with refrigerant oil.
2. Attach the stubbed end of the kit valve to the liquid line
orifice housing. Finger tighten and use an appropriately
sized wrench to turn an additional 1/2 turn clockwise
as illustrated in figure 17, or 20 ft−lb.
3. Place the remaining Teflon washer around the other
end of the TXV. Lightly lubricate connector threads
and expose surface of the Teflon ring with refrigerant
oil.
4. Attach the liquid line assembly to the TXV. Finger
tighten and use an appropriately sized wrench to turn
an additional 1/2 turn clockwise as illustrated in figure
17, or 20 ft−lb.
5. Attach the suction line sensing bulb in the proper
orientation as illustrated in figure 21 using the clamp
an screws provided.
NOTE − Insulating the sensing bulb once installed may be
required when the bulb location is external to the coil
casing.
Page 10
FIXED ORIFICE (1)
FIXED ORIFICE
EXTRACTOR (1)
TEFLON RING (1)
FIXED ORIFICE STICKER (1)