j. Assemble vent run to exterior wall - If not
previously measured, locate the center of the
vent at the exterior wall. Prepare an opening
as described in Step B. Assemble the vent
system to point where the terminus of the last
section is within 7" (178 mm) to 11-1/4" (286
mm) inboard of the exterior surface to which
the SV4.5 HT termination is to be attached, see
Figure 35. If the terminus of the last section
is not within this distance, use the telescopic
vent section SV4.5LA, as the last vent section.
For wall thicknesses greater than that shown in
Figure 36, refer to Table 8 on Page 20. This table
lists the additional venting components needed
(in addition to the termination and adaptor) for
a particular range of wall thicknesses.
K. Attach termination adaptor - Attach the
adaptor (adaptor - SV4.5RCH - provided with the
termination) to the vent section or telescoping
vent section), elbow or appliance collar as shown
in Figures 35 and 36 in the same manner as
any SV4.5 vent component (refer to Step E).
L. Install Firestop/Spacer at exterior wall
- When using the square termination, install
SV4.5HF (Secure Vent
), SF4.5HF (Secure
®
Flex
) Firestop/Spacer over the opening at the
®
exterior side of the framing, long side up, with
the 3" spacer clearance at the top as shown in
Figure 35, and nail into place. The Firestop/
Spacer may also be installed over the opening at
the interior side of the framing. The gap between
the vent pipe and a firestop can be sealed with
noncombustible caulking.
M. Install the desired termination -
1. Install the square termination (SV4.5HT-2)-
For the last step , from outside the exterior
wall, slide the collars of the termination onto
the adaptor (the outer over the outer and the
inner inside the inner) until the termination
seats against the exterior wall surface to which
it will be attached. Orient the housing of the
termination with the arrow pointed upwards.
Secure the termination to the exterior wall. The
horizontal termination must not be recessed
into the exterior wall or siding by more than
the 1-1/4" (32 mm) as shown in Figure 36.
SVHRK Snorkel Cap -The snorkel cap is
designed to be fitted into a basement window
box. The SVHRK cap is for use with flex vent
The vertical distance between the inlet and outlet
of the cap is 28" (711 mm). pipe.
IMPORTANT: The vent termination is hot
while in operation and for a period of
time following the use of the fireplace.
To prevent contact with hot surfaces,
we recommend the use of a Termina-
tion Guard. See Page 35. This can be
purchased at your local dealer.
7"
(178)
12-1/8"
(308 mm)
5-1/8"
(130 mm)
Adaptor
SV4.5RCH
6 to 48" Vent Section,
Telescopic vent section,
Elbow or Appliance Collar
Figure 35
Installing the Square Horizontal Termination (SV4.5HT-2)
* Use silicone caulking to
seal the top and sides of the
termination, up to the under-
layment, stucco, or masonry
wall surface.
Maximum Extent of
Siding
Vent Run Sections
*Caulk
Relative to Exterior
Surface of Framing
Last Vent Section. Use
Telescopic Vent Section
(SV4.5LA), If Necessary
*Caulk
SV4.5HT-2
Square Termination
Stucco
**For thicknesses greater
than 10", see Table 8.
Venting Connection and Exterior Wall Recessing of the
Horizontal Square Termination (SV4.5HT-2).
Figure 36
Horizontal terminations have been designed to perform in a wide range of weather
conditions. Our terminations meet or exceed industry standards.
When selecting the locations of your horizontal terminations, do not place the termination
where water from eaves and adjoining rooflines may create a heavy flow of cascading water
onto the termination cap. If the cap must be placed where the possibility of cascading water
exists, it is the responsibility of the builder to direct the water away from the termination
cap by using gutters or other means.
Take care to carefully follow the installation instructions for the termination, including the
use of silicone caulking where required.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
To help minimize water infil-
tration it is recommended that
the Firestop/Spacer (SV4.5HF)
be installed on the exterior
side of the wall.
10-1/2"
(267mm)
NOTE: Centerline of Vent Piping is NOT
the Same as the Centerline of the
Framed Opening.
See Figure 14 on Page 10 for Min.
Distance to Base of Appliance.
Base of Appliance
Interior Surface of
Finished Wall
Adaptor
SV4.5RCH
SV4.5HT-2
Termination
3"
(76 mm)
1"
(25.4 mm)
Maximum Wall Thickness
10"(254 mm)**
Exterior Surface of Siding
Exterior Surface of
Framing
6" to 9-1/4"
(152 to 235 mm)**
SV4.5HT-2
Square Termination
1-1/4" Maximum Recess
of the Square Termination
into Exterior Finishing
Material
19