Analog I/O Function; Analog Input; Analog Output - Mitsubishi Electric FR - F700 Programming Manual

Plc function programming manual
Table of Contents

Advertisement

Analog I/O function

1.13 Analog I/O function

1.13.1 Analog input

Analog input value of terminal 1, 2, 4 can be read from D9245 to D9247.
Device
Terminal Name
No.
D9245 Terminal 1 input
D9246 Terminal 2 input
D9247 Terminal 4 input
Actual read processing is performed at the END processing of the sequence.
REMARKS
Full-scale value of analog input is determined by the setting of Pr. 73 Analog input selection, Pr.
267 Terminal 4 input selection. Refer to the Instruction Manual of the inverter.

1.13.2 Analog output

Analog output from each terminal can be performed by setting value on D9251 to
D9254.
Output from PLC function can be performed by setting "70" in output signal selection
parameters of each terminal (terminal CA: Pr. 54, terminal AM: Pr. 158, terminal AM0,
AM1: Pr. 306, Pr. 310).
Device
Terminal Name
No.
D9251 Terminal CA
D9252 Terminal AM
Terminal AM0
D9253
(FR-A7AY)
Terminal AM1
D9254
(FR-A7AY)
Actual read processing is performed at the END processing of the sequence.
46
Setting
Data Access Enable
Unit
Condition
0.1%
0.1%
Always
0.1%
Setting
Data Access Enable
Unit
Condition
0.1%
0.1%
0.1%
Always
0.1%

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-f700

Table of Contents