[ VII Microprocessor Control ]
In the air : Detected that the float switch is OFF for 15 seconds.
Float SW
ON
OFF

2. Dry operation

TIME SUN MON TUE WED THU FRI SAT
TIMER
AFTER
˚F˚C
ONLY1Hr.
TEMP.
MENU
BACK
MONITOR/SET
PAR-21MAA
CLOCK
1. Termoregulating function
(1) Thermo regulating function (Function to prevent restarting for 3 minutes)
Setting the Dry thermo by the thermo regulating signal and the room temperature (TH21).
Dry thermo ON Room temperature
Dry thermo OFF Room temperature
Room temperature
Over 64°F
Less than 64°F
(2) Frozen prevention control
No control function
2. Fan
(1) Indoor fan operation controlled depends on the compressor conditions.
Dry thermo
ON
OFF
HWE08010
15sec.
15sec.
In the water
In the air
Hr
ON
AFTER
OFF
ERROR CODE
FUNCTION
˚F˚C
FILTER
WEEKLY
SIMPLE
AUTO OFF
ON/OFF
ON/OFF
FILTER
DAY
CHECK
TEST
OPERATION
CLEAR
desired temperature + 2°F
desired temperature
3 min. passed since starting operation
Thermo regulating signal
ON
OFF
Excluding the following
15sec. 1min.30sec.
In the water
postponement
<How to operate>
1. Press POWER [ON/OFF] button.
2. Press the operation [Mode] button to display DRY.
3. Press the [Set Temperature] button to set the desired tempera-
ture.
The set temperature changes 2°F when the [Set Temperature]
button is pressed one time. Dry 67 to 87°F
Room temperature (T1)
T1
83°F
83°F > T1
79°F
79°F > T1
75°F
75°F > T1
Unconditional
Dry thermo OFF
Fan speed notch
Room temp. < 64°F
- 11 -
1min.30sec.
Drain pump
Error
abnormal
Dry thermo
ON time (min)
OFF time (min)
9
7
5
3
3
[Low]
Stop
[Low]
Dry thermo
3
3
3
3
10
GB