[ VIII Troubleshooting ]
2. Capacity code setting
(1) SW2
1) Indoor control board
Dipswitch settings must be made while the unit is stopped.
Factory setting
The switches are set to correspond to the unit capacity.
PEFY-P06NMSU-E
PEFY-P08NMSU-E
PEFY-P15NMSU-E
PEFY-P18NMSU-E
3. Model setting
(1) SW4
1) Indoor control board
Dipswitch settings must be made while the unit is stopped.
Factory setting
Note:
Changes made to the dipswitches SW1, SW2, and SW3 will become effective when the unit comes to a stop (remote controller
off). There is no need to power cycle the unit.
4. External static pressure
(1) SWA, SWC
1) Address board
All models
5[0.02]
3
2
2
1
1
SWA SWC
Note:
Changes that are made to the dipswitches SWA and SWC immediately become effective regardless of the unit's operation
status (RUN/STOP) or the remote controller status (ON/OFF).
5. 1's and 10's digits
(1) SW11, SW12 (Rotary switch)
The use of a network remote controller (PAR-F27MEA) requires address setting.
1) Address board
Address settings must be made while the unit is stopped.
Factory setting
HWE08010
PEFY-P12NMSU-E
PEFY-P24NMSU-E
15[0.06]
35[0.14]
3
3
2
2
2
2
1
1
1
1
SWA
SWC
SWA
SWC
Factory
Pa[in.WG]
setting
50[0.20]
3
2
2
1
1
SWA
SWC
- 27 -
(A)
2
3
2
(B)
1
1
SWA
SWC
(A) Option
(B) Standard
GB