Deciding on Where to Install the Air Conditioner
A
RJ050F2HX ** /AJ050FCJ2 **
Indoor unit
Outdoor unit
** 020/023/026/
RJ050F2HX **
035/052
AJ050FCJ2 **
07/09/12/18 **
RJ050F2HX ** /AJ050FCJ2 ** Outdoor unit cannot be connected to the following indoor unit combination.
- MH052FMEA/MH052FUEA/**24**/AJN052NDEHA
100 mm
or more
CAUTION
3 m as minimum pipe length: It will reduce noise and
vibration.
300 mm
minimum
600 mm
minimum
The appearance of the unit may be different from the diagram depending on the model.
Piping length and the height
Dimension
Composition
The appearance of the unit may be different from the diagram depending on the model.
6
Power supply Ø, V, Hz
1,220-240,50/60
200 mm
or more
600 mm
minimum
300 mm
minimum
1 Room max
2 Room total max
length
length
20m
A,B
Make at least one round:
It will reduce noise and vibration
Piping outside diameter
Unit
** 020/023/026/
030/035/07/09/12 **
** 052/18 **
160 mm
or more
A
Max height between
indoor unit & outdoor unit
30m
15m
A+B
(H)
Outside diameter
Liquid
Gas
3/8"
1/4"
1/2"
B
Main power switch
Max height between
indoor units
7.5m
(h)
(h)
(H)