Heating Mode - Mitsubishi Electric PUG18AK Technical Manual

Split-type,heat pump air conditioners pug & pugh condensing units
Table of Contents

Advertisement

4
PERFORMANCE DATA – OPERATING PRESSURES

HEATING MODE

PKH18FK/PUGH18
Outdoor
Heating
Air
Air
Capacity
Flow
(deg °F)
(BTUH)
(CFM)
65
23,529
60
22,197
55
20,864
50
19,532
47
18,800
45
18,200
40
16,700
710
35
15,200
30
14,089
25
12,978
20
11,867
17
11,200
PKH30FK/PUGH30
Outdoor
Heating
Air
Air
Capacity
Flow
(deg °F)
(BTUH)
(CFM)
65
36,629
60
34,555
55
32,481
50
30,407
47
29,200
45
28,333
40
26,167
990
35
24,000
30
22,333
25
20,667
20
19,000
17
18,000
INDOOR AIR 70°
Compressor
Current
Pressure (psig)
(Amps)
Disch.
Suction
8.8
299
76
8.3
282
72
7.8
265
68
7.3
249
63
7.0
237
61
6.8
232
59
6.5
218
53
6.1
205
48
5.8
196
44
5.5
188
40
5.2
180
36
5.1
176
33
INDOOR AIR 70°
Compressor
Current
Pressure (psig)
(Amps)
Disch.
Suction
12.6
297
69
11.9
280
65
11.2
263
61
10.5
246
57
9.9
234
55
9.8
229
53
9.5
218
49
9.2
206
44
9.0
199
40
8.7
191
36
8.5
183
32
8.3
178
30
PKH24FK/PUGH24
Outdoor
Air
(deg °F)
65
60
55
50
47
45
40
35
30
25
20
17
PKH36FK/PUGH36
Outdoor
Air
(deg °F)
65
60
55
50
47
45
40
35
30
25
20
17
SP007-21
Heating
Air
Compressor
Capacity
Flow
Current
(BTUH)
(CFM)
(Amps)
30,165
11.8
28,457
11.2
26,749
10.5
25,041
9.8
24,000
9.3
23,333
9.2
21,667
710
8.8
20,000
8.4
18,556
8.1
17,111
7.8
15,667
7.5
14,800
7.3
Heating
Air
Compressor
Capacity
Flow
Current
(BTUH)
(CFM)
(Amps)
43,567
15.9
41,101
15.0
38,634
14.1
36,167
13.2
34,600
12.4
33,700
12.3
31,450
990
11.9
29,200
11.6
27,200
11.3
25,200
10.9
23,200
10.6
22,000
10.4
INDOOR AIR 70°
Pressure (psig)
Disch.
Suction
329
74
310
70
291
66
273
62
260
60
254
58
241
52
227
47
218
43
210
40
201
36
196
34
INDOOR AIR 70°
Pressure (psig)
Disch.
Suction
324
75
306
71
287
67
269
62
255
60
251
58
239
53
228
49
228
44
228
40
228
36
228
33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents