Mode Setting - Sanyo 26 series Installation Instructions Manual

Split system heat pump air conditioner
Table of Contents

Advertisement

8-4. Mode Setting

According to the function of each system controller, set
SW1 as shown in Fig. 8-5.
(1) Central control/Remote control mode
Central control mode
The system controller is used as the central control
equipment.
Individual setting by remote controller can be
inhibited by the system controller
Remote control mode
The system controller is used as the remote controller.
Setting by system controller is inhibited by other
central control equipment.
(2) ALL/ZONE mode
ALL mode
All indoor units can be controlled by the system
controller.
ZONE mode
Indoor units in one of ZONE 1, 2, 3 or 4 can be
controlled by the system controller
(3) The function of the system controller consists of 10 types
according to the combination of central control/remote
control mode and ALL/ZONE mode setting as shown
in the table 8-1.
(4) Stick the system controller unit label in a con-
spicuous position.
SC
Central control
Remote control
mode
mode
2
3 4 5 6
2
3 4 5 6
ON
ON
OFF
OFF
ALL
ALL
central control
remote control
2
3 4 5 6
2
3 4 5 6
ON
ON
OFF
OFF
ZONE1
ZONE1
central control
remote control
2
3 4 5 6
2
3 4 5 6
ON
ON
OFF
OFF
ZONE2
ZONE2
central control
remote control
2
3 4 5 6
2
3 4 5 6
ON
ON
OFF
OFF
ZONE3
ZONE3
central control
remote control
2
3 4 5 6
2
3 4 5 6
ON
ON
OFF
OFF
ZONE4
ZONE4
central control
remote control
Fig. 8-5
Table 8-1
Central control
ALL
1. ALL/Central
ZONE1
2. ZONE1/Central
ZONE2
3. ZONE2/Central
ZONE3
4. ZONE3/Central
ZONE4
5. ZONE4/Central
88
Inter-unit control wiring
1
2
16
ZONE1
central control
address 1-16
17
18
32
ZONE2
central control
address 17-32
33
34
48
ZONE3
central control
address 33-48
49
50
64
ZONE4
central control
address 49-64
Remote control
6. ALL/Remote
7. ZONE1/Remote
8. ZONE2/Remote
9. ZONE3/Remote
10. ZONE4/Remote

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents