Vitocrossal 300, CT3 Series Installation
Technical Data
(continued)
Boiler Model
Weight
boiler shell
Overall weight complete with
insul. and control (w/o burner)
Boiler water content
Heat exchanger surface
water-cooled
Max. operating temperature
Max. operating pressure
Flue gas resistance
Boiler connections
boiler supply (BS) & return (BR1)
Boiler return (BR2)
*3
Safety supply
Boiler drain
Condensate drain
Vent pipe
internal Ø
*4
Flue gas values
Temperature (at a return
temperature of 86° F (30° C)
- at rated input
- at partial load
Temperature (at a return
temperature of 140° F (60° C)
Mass flow rate (of flue gas)
Gas volume of combustion
chamber and heat exchanger
Pressure at boiler flue outlet
- at partial input
- at maximum input
*3
Boiler has two return connections - the heating return with the lower temperature should be connected to the boiler
return BR1.
*4
Values for calculating the size of the flue system based on 10% CO
measured as gross values at 68º F (20º C) combustion air temperature. The details for partial load refer to an output
of 30% of rated input. Calculate the flue gas mass flow rate accordingly when the partial load differs from that
stated above (subject to the burner mode).
For information regarding other Viessmann System Technology componentry, please reference documentation
of respective product.
CT3-
17
22
lbs
1012
1114
(kg)
(459)
(505)
lbs
1228
1352
(kg)
(557)
(613)
USG
71.3
78.2
(L)
(270)
(298)
ft.
2
89.3
106.6
(m
2
)
(8.3)
(9.9)
ft.
2
(m
2
)
psig
kpa
"w.c.
0.40
0.56
Pa
(100)
(140)
in.
2b
2b
(mm)
(65)
(65)
in.
2
2
(mm)
(50)
(50)
in.
1a
1a
(mm)
(32)
(32)
in.
1
1
(mm)
(b)
(b)
in.
8
8
(mm)
(201)
(201)
°F
113
113
(°C)
(45)
(45)
°F
104
104
(°C)
(40)
(40)
°F
167
167
(°C)
(75)
(75)
lbs/h
704
928
(kg/h)
(320)
(422)
ft.
3
8.83
9.92
(m
3
)
(0.250)
(0.281)
Pa
-3
0
Pa
(-3)
(-4)
28
37
48
1202
1671
1759
(545)
(758)
(798)
1455
1962
2064
(660)
(890)
(936)
87.2
129.5
140.8
(330)
(490)
(533)
127.0
162.5
184.1
(11.8)
(15.1)
(17.1)
210
(99)
30
(207)
0.64
0.80
0.88
(160)
(200)
(220)
3
4
4
(80)
(100)
(100)
2
3
3
(50)
(75)
(75)
2
2
2
(51)
(50)
(50)
1
1
1
(b)
(b)
(b)
8
10
10
(201)
(251)
(251)
113
113
113
(45)
(45)
(45)
104
104
104
(40)
(40)
(40)
167
167
167
(75)
(75)
(75)
1179
1531
1903
(536)
(696)
(865)
12.00
15.90
18.40
(0.340)
(0.450)
(0.521)
-5
0
0
-2
0
0
for natural gas. Flue gas temperatures
2
Appendix
57
72
89
1995
2706
3014
(905)
(1230)
(1370)
2322
3014
3344
(1053)
(1370)
(1520)
150.6
199.2
221.9
(570)
(754)
(840)
220.7
305.7
372.5
(20.5)
(28.4)
(34.6)
1.08
1.20
1.32
(270)
(300)
(330)
4
5
5
(100)
(125)
(125)
3
4
4
(75)
(100)
(100)
2
2b
2b
(50)
(65)
(65)
1
1
1
(b)
(b)
(b)
10
12
12
(251)
(301)
(301)
113
113
113
(45)
(45)
(45)
104
104
104
(40)
(40)
(40)
167
167
167
(75)
(75)
(75)
2380
2979
3705
(1082)
(1354)
(1684)
21.54
40.61
42.73
(0.610)
(1.150)
(1.210)
0
0
0
0
0
0
31