Vitocrossal 300, CT3 Series Installation

Initial Start-Up

Flow rate
Legend
A CT3-17 to -22
B CT3-28
C CT3-37 to -57
D CT3-72 to -89

Recommended Flow Rates

Boiler model
CT3-
20° F ∆t
GPM
40° F ∆t
GPM
11° C ∆t
L/s
22° C ∆t
L/s
 ∆t = temperature difference
 This boiler does not require a flow switch.
17
22
28
61
81
103
31
41
52
3.9
5.1
6.5
2.0
2.6
3.3

Pressure drop (primary circuit)

The Vitocrossal 300 boiler is only suitable for heating
systems with pumped heating water.
For start-up and adjustments, see the service
instructions for boiler, burner and boiler control
unit
CAUTION
Do not fire the burner unless boiler and heating system
are properly filled with water and purged of any air.
37
46
134
166
67
83
8.5
10.5
4.2
5.3

Start-Up

57
72
208
260
323
104
130
162
13.2
16.5
20.4
6.6
8.2
10.3
89
29