3.4. Digital inputs configuration

For the inputs configuration you must assign:
• An alarm mnemonic name
• The type of change of the contact to be detected
• The addressees of the alarm message
Before starting with the inputs setting, be sure that the sensors connected to the inputs contacts are in the "alarm off" status. Once
Pocket AL I/O receives the message of input configuration, it will store the actual input situation as "alarm off" status, whether it
is OPEN or CLOSED.
Pocket AL I/O can be set to send the alarm ON message when the changing from "alarm off" to "alarm on" is detected and to
send the alarm OFF message when the contact returns in "alarm off" status.
It can be set to send only the alarm ON message when the Status change from "alarm off" to "alarm on" is detected. Then when
the status will return "alarm off", no message is sent. We suggest to use the Status configuration when the sensor connected to
Pocket AL I/O is a photocell.
Transition detection
alarm ON
#
KEY
#
Message format to set the digital inputs:
NAME
VALUE
Key
1,2,3,4
9,10
ID
A..Z,a..z,
0..9
Detection
T,S,t,s
User n
+ 0..9
NOTES
1. If you want to add a number to a set list, it will be necessary to insert all the numbers again.
2. By setting the filed user1="0" it will manage the input the status of which can be tear with the "test"
command but no sms will be sent.
EXAMPLES
#1#GasAlarm#T#+393359988776#
#2#GatePhotocell#S#+393359988776#+393491122334#+393285554446#
#3#AntitheftAlarm#T#+393359988776#+393491122334#
3.6
alarm OFF
≥ 200ms
ID
#
DETECTION
DESCRIPTION
Key of non optoinsulated digital inputs: 1,2,3,4
Key of optoinsulated digital inputs: 9,10
ID associated to the contact (20 characters maximum. "#" and space characters not
accepted in the ID field)
Type of detection to be signalled:
T o t: detection of any transition;
S o s: detection of status change.
Phone numbers to which the alarm message is sent (up to six phone numbers can be
inserted)
Status change detection
alarm ON
≥ 200ms
#
USER1
#
USERn
Configuration
#
USER6
#