Heating Operation; Intermittent Fan Mode - Fujitsu Airstage V-II Service Manual

Multi air conditioning system for buildings
Hide thumbs Also See for Airstage V-II:
Table of Contents

Advertisement

Intermittent fan mode

Fan step
Fan mode
6
intermittent 6
5
intermittent 5
4
intermittent 4
3
intermittent 3
2
intermittent 2
1
intermittent 1
Normal fan step
300 rpm
0 rpm
When switched from normal fan step to intermittent fan step, always start from 300rpm/7sec.
When there was a change during intermittent step 1-6, switching is performed at the time the current speed
duration time reaches time-up.

2-3-2 Heating Operation

Fan step
AJ A72LALH AJ A90LALH AJ A108LALH AJ A126LALH AJ A144LALH
16
15
14
13
12
11
10
9
8
7
Switching conditions of step
The initial speed of the first boot outdoor unit is detected by outdoor air temperature sensor value (TAOUT).
Outside air temperature
sensor detected value
TAOUT
10°C
10°C
TAOUT
15°C
15°C
TAOUT
20°C
20°C
TAOUT
Thereafter, the high-pressure is monitoring at a set time interval and the fan speed is changed by the following conditions.
Other outdoor units are normally operated at fan step 16.
(Condition which lowers the fan speed)
High-pressure
3.30MPa and heat sink temperature
(Condition which raises the fan speed)
High-pressure saturation
Fan speed 0 rpm
duration time T ( sec )
6
12
19
26
33
40
Intermitten fan step
7 sec
7 sec
[ T ] sec
Fan speed (rpm)
880
880
860
860
830
830
700
700
600
600
500
500
420
420
360
360
320
320
300
300
Fan step
16
12
7
7
3.20MPa or heat sink temperature
Fan speed 300 rpm
duration time ( sec )
7
7 sec
[ T ] sec
880
920
860
870
830
820
700
700
600
600
500
500
420
420
360
360
320
320
300
300
75°C
80°C
02-07
Time
920
870
820
700
600
500
420
360
320
300