3-Phase Diode Bridge

Check Point 1 : Appearance check
No fissures, breaks, damage, etc. at body and terminal section?
Is the rear of the body coated with silicone grease?
Are there no abnormalities at threaded parts (stripped threads, deformation, damage, etc.) ?
Check Point 2 : Electric check
In the 3-phase diode bridge single part state, set the tester to the "Resistance" mode,
and check for open/short between the following terminals.
Tester + side
Tester - side
(red)
(black)
Pin 1
Pin 2
Pin 4
Pin 3
Pin 1
Pin 5
Pin 2
Pin 3
Judge the result of
as follows:
All 6 points shorted
1 or more points open
Set the tester to the "Resistance" mode, and check for open/short between the following terminals.
Tester + side
Tester - side
(red)
(black)
Pin 1
Pin 4
Pin 2
Pin 3
Pin 1
Pin 2
Pin 5
Pin 3
Judge the result of
as follows:
All 6 points open
1 or more points shorted : Defective
: Normal
: Defective
: Normal
1
2
1
2
4
4
+ 4
04-105
3
3
5
5
Diode bridge
- 5

Hide quick links: