Reactor (Inv); Reactor (Dc Fan) - Fujitsu Airstage V-II Service Manual

Multi air conditioning system for buildings
Hide thumbs Also See for Airstage V-II:
Table of Contents

Advertisement

SERVICE PARTS INFORMATION 9

Reactor (INV)

Reactor (DC Fan)

Check Point 1 : Appearance check
No fissures, breaks, damage, etc. at the body and winding section, terminals section?
Check Point 2 : Electric check
Set the tester to the "Resistance" mode, and check for open/short between both ends of the reactor wire
(or connector).
Judge the result of
as follows:
Short
: Normal
Open
: Abnormal (open)