Function List - Mitsubishi Electric GB-50A Instruction Book

Air-conditioner network system central controller
Hide thumbs Also See for GB-50A:

Advertisement

3-2.Function list

The use of GB-50A requires a license registration. By registering the license, group or block operation of
the units on the Web browser will become available. Registration for the license that is required to use
various functions can be completed on the license registration page.
Item
Start/stop
Operation mode
Temperature setting
Air velocity
Air direction
Start/stop of interlocked
equipment (Lossnay)
Prohibition of local control
Error display
Filter sign display and
reset
Malfunction history
Annual/weekly schedule
Malfunction e-mail history
* The above specification may be changed depending on the equipment connected or combined.
* The block setting and the registration of block/group names require the initial setting tool or initial setting
web.
*Without prior notice, the content may be changed.
Table 3-2 List of Web monitoring function
Switching start/stop collectively or for each group
Switching cool/dry/fan/auto/heat collectively or for each group
Setting room temperature collectively or for each group
Set temperature range Cool/dry: 19ºC-30ºC /67ºF-87ºF
Switching air velocity in 4 steps collectively or for each group.
Switching in 4 steps vertically and for swing collectively or for each group
(Selectable air direction differs depending on the model)
Switching start (Hi/Lo)/stop collectively or for each group when connecting with
interlocked equipment (Lossnay).
(However, ventilation mode can not be selected for the interlocked equipment.)
Selecting the items for which local control is prohibited collectively or for each
group.
(Items include start/stop, operation mode, temperature setting and filter sign.)
Identifies the unit in trouble and displays the nature of trouble
Filter sign display can be reset in each group or collectively.
Malfunction history can be check up to 64 contents in both unit and
communication error.
Using the annual/weekly schedule function by license registration.
E-mail history can be check up to 64 contents.
Content
Heat:
17ºC-28ºC /63ºF-83ºF
Auto:
19ºC-28ºC /67ºF-83ºF
*Note: Preset temperature range varies on different models.