Universal Mode Wiring Arm/Disarm/Panic - NAPCO 2WAY-UNIVKF Installation Instructions Manual

Bi-directional lcd keyfob
Hide thumbs Also See for 2WAY-UNIVKF:
Table of Contents

Advertisement

Universal operation requires the use of control panel zones to provide Arm / Disarm and Panic operation. One zone must be
programmed as a keyswitch arm zone which will process a 2 second violation as an Arm / Disarm command. The other zone must
be programmed as a 24 hour panic zone, which will process a 2 second violation as a panic alarm. The wiring instructions below
include wiring schemes for control panels which support zone doubling, such as the NAPCO Express
Wiring for Arm / Disarm
Program a zone on the control panel for "Keyswitch Arm"
When [ON/OFF] is pressed, the Arm/Disarm relay will
change state (from normally closed to normally open) for 2
seconds and then restore, causing the control panel to arm
or disarm.
EOLR PANEL
Typical Keyswitch wiring
for a zone using
End of Line resistors
N/O
COM
N/C
8
9
10
EOLR
Zone programmed for
Keyswitch Arm
STEP 1
- WIRING FOR ARM / DISARM AND PANIC
ZONE DOUBLED PANEL
Typical Keyswitch wiring
for a "zone doubled" zone
N/O
COM
N/C
8
9
10
ZDR*
Zone programmed for
Keyswitch Arm
* ZDR = Zone Doubling Resistor
Wiring for Panic
Program a zone on the control panel as a 24 Hour Panic
Zone.
When [PANIC] is pressed, the Panic relay will change
state (from normally closed to normally open) for 2
seconds and then restore, causing an alarm on the the
control panel Panic Zone.
EOLR PANEL
Typical Panic wiring
for a zone using
End of Line resistors
N/O
COM
N/C
11
12
13
EOLR
Zone programmed for
24 hour panic
series.
ZONE DOUBLED PANEL
Typical Panic wiring
for a "zone doubled" zone
N/O
COM
N/C
11
12
13
ZDR
Zone programmed for
24 hour panic
* ZDR = Zone Doubling Resistor