Units With Factory- - Installed; Non- - Fused Disconnect Or Hacr - Carrier 48HC Installation Instructions Manual

Single package rooftop gas heating/electric cooling unit with puronr (r-410a) refrigerant sizes: 04, 05, 06
Table of Contents

Advertisement

Units Without Single Point Box, Disconnect or HACR Option
Equip
C
GR Lug
C
11
23
11
13
Disconnect
per
NEC
208/230-1-60
Ground
L1
L2
(GR)
208/230-3-60
460-3-60
575-3-60
Units With Disconnect or HACR Option
L1
2
Optional
4
Disconnect
L2
3 Phase Only
Switch
L3
6
Ground
(GR)
Disconnect factory test leads; discard.
Fig. 24 - - Power Wiring Connections
WARNING
!
FIRE HAZARD
Failure to follow this warning could result in
intermittent operation or performance satisfaction.
Do not connect aluminum wire between disconnect
switch and air conditioning unit. Use only copper wire.
(See Fig. 25.)
ELECTRIC
DISCONNECT
SWITCH
WIRE ONLY
ALUMINUM
Fig. 25 - - Disconnect Switch and Unit
Units with Factory- - Installed Non- - Fused Disconnect or
HACR—
The factory- - installed option non- - fused disconnect (NFD)
or HACR switch is located in a weatherproof enclosure
located under the main control box. The manual switch
handle and shaft are shipped in the disconnect or HACR
enclosure. Assemble the shaft and handle to the switch at
this point. Discard the factory test leads (see Fig. 24).
Connect field power supply conductors to LINE side
terminals when the switch enclosure cover is removed to
attach the handle.
1-ph Belt Drive IFM
Direct Drive IFM
or
IFC
Equip
13
23
TB
GR Lug
Disconnect
per
NEC
L3
Ground
(GR)
1
3
3 Phase Only
Factory
Wiring
5
Equip GR Lug
C12249
COPPER
WIRE
A93033
Fig. 26 - - Location of Non- - Fused Disconnect Enclosure
To field install the NFD shaft and handle:
1. Remove the unit front pane (see Fig. 2).
2. Remove (3) hex screws on the NFD enclosure - - (2) on
the face of the cover and (1) on the left side cover.
3. Remove the front cover of the NFD enclosure.
4. Make sure the NFD shipped from the factory is at
OFF position (the arrow on the black handle knob is
at OFF).
5. Insert the shaft with the cross pin on the top of the shaft
in the horizontal position.
6. Measure from the tip of the shaft to the top surface of
the black pointer; the measurement should be 3.75 - -
3.88 in. (95 - - 99 mm).
7. Tighten the locking screw to secure the shaft to the
NFD.
8. Turn the handle to the OFF position with red arrow
pointing at OFF.
9. Install the handle on to the painted cover horizontally
with the red arrow pointing to the left.
10. Secure the handle to the painted cover with (2) screws
and lock washers supplied.
11. Engaging the shaft into the handle socket, re- - install
(3) hex screws on the NFD enclosure.
12. Re- - install the unit front panel.
Fig. 27 - - Handle and Shaft Assembly for NFD
16
C12278
C12279

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

48hc series48hc-a0448hc-a0548hc-a06