New Or Replacement Line Set - Lennox Elite XC13 Installation Instructions Manual

Elite series
Table of Contents

Advertisement

2. With a continuous motion slightly rotate and guide the
lip of top tab inward as illustrated in figure 12, details
A and C, then upward into the top slot of the hinge
corner post.
3. Rotate panel to vertical to fully engage all tabs.
4. Holding the panel's hinged side firmly in place, close
the right−hand side of the panel, aligning the screw
holes.
IMPORTANT! Do not allow panels to hang on unit by top tab. Tab
is for alignment and not designed to support weight of panel.
Panel shown slightly rotated to allow top tab to exit (or enter) top
slot for removing (or installing) panel.
SCREW
HOLES
LIP
DETAIL A
DETAIL B
Detail C
Figure 12. Removing/Installing SmartHingetPanels
(Details A, B and C)
Maintain minimum panel angle (as close to parallel with the unit
as possible) while installing panel.
ANGLE MAY BE TOO
EXTREME
PREFERRED ANGLE
FOR INSTALLATION
Figure 13. Removing/Installing SmartHingetPanels
(Detail D)
506120−01 03/10
ROTATE IN THIS DIRECTION;
THEN DOWN TO REMOVE
PANEL
HOLD DOOR FIRMLY TO THE HINGED
SIDE TO MAINTAIN
FULLY−ENGAGED TABS
5. When panel is correctly positioned and aligned, insert
the screws and tighten.

New or Replacement Line Set

This section provides information on installation or
replacement of existing line set. If line set are not being
installed then proceed to Brazing Connections on page 10.
If refrigerant lines are routed through a wall, seal and
isolate the opening so vibration is not transmitted to the
building. Pay close attention to line set isolation during
installation of any HVAC system. When properly isolated
from building structures (walls, ceilings. floors), the
refrigerant lines will not create unnecessary vibration and
subsequent sounds. Also, consider the following when
placing and installing a high−efficiency air conditioner.
REFRIGERANT LINE SET
Field refrigerant piping consists of liquid and suction lines
from the outdoor unit (braze connections) to the indoor unit
coil (flare or sweat connections). Use Lennox L15 (sweat,
non−flare) series line set, or use field−fabricated refrigerant
lines as listed in table 2.
Table 2. Refrigerant Line Set
Valve Field
Connections
XC13
Liquid
Line
−018
3/8 in.
−024
(10 mm)
−030
−036
3/8 in.
−042
(10 mm)
−048
3/8 in.
−060
(10 mm)
NOTE − When installing refrigerant lines longer than 50
feet, see the Lennox Refrigerant Piping Design and
Fabrication Guidelines, or contact Lennox Technical
Support Product Applications for assistance. To obtain the
correct information from Lennox, be sure to communicate
the following points:
S
Model (XC13) and size of unit (e.g. −060).
S
Line set diameters for the unit being installed as listed
in table 2 and total length of installation.
S
Number of elbows and if there is a rise or drop of the
piping.
MATCHING WITH NEW OR EXISTING INDOOR COIL
AND LINE SET
The RFC1−metering line consisted of a small bore copper
line that ran from condenser to evaporator coil. Refrigerant
was
metered
temperature/pressure evaporation effects on refrigerant in
the small RFC line. The length and bore of the RFC line
corresponded to the size of cooling unit.
Page 8
Recommended Line Set
Suction
Liquid
Suction
Line
Line
Line
3/4 in.
3/8 in
3/4 in.
(19 mm)
(10 mm)
(19 mm)
7/8 in
3/8 in.
7/8in
(22 mm)
(10 mm)
(22 mm)
1−1/8 in.
3/8 in.
1−1/8 in.
(29 mm)
(10 mm)
(29 mm)
into
the
evaporator
L15
Line Sets
L15−41
15 ft. − 50
ft.
(4.6 m − 15
m)
L15−65
15 ft. − 50
ft.
(4.6 m − 15
m)
Field
Fabricated
by
utilizing

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents