Flushing The System - Lennox Elite XC13 Installation Instructions Manual

Elite series
Table of Contents

Advertisement

4. Remove and discard fixed orifice, valve stem
assembly if present and Teflon ring as illustrated in
figure 18.
5. Use a field−provided fitting to temporary reconnect the
liquid line to the indoor unit's liquid line orifice housing.
TYPICAL TXV REMOVAL PROCEDURE
Use the following procedure to remove the indoor unit's
TXV and install a temporary field provided fitting.
(Uncased Coil Shown)
TWO PIECE
PATCH PLATE
LIQUID LINE
(UNCASED COIL
ORIFICE
ONLY)
HOUSING
DISTRIBUTOR
TUBES
DISTRIBUTOR
EQUALIZER
ASSEMBLY
LINE
MALE EQUALIZER
LINE FITTING
SENSING
BULB
Figure 19. Typical TXV Removal
1. On fully cased coils, remove the coil access and
plumbing panels.
2. Remove any shipping clamps holding the liquid line
and distributor assembly.
3. Disconnect the equalizer line from the TXV equalizer
line fitting on the suction line.
4. Remove the suction line sensing bulb as illustrated in
figure 19.
5. Disconnect the liquid line from the TXV at the liquid line
assembly.
6. Disconnect the TXV from the liquid line orifice housing.
Take care not to twist or damage distributor tubes
during this process.
7. Remove and discard TXV and the two Teflon rings as
illustrated in figure 19.
8. Use a field−provided fitting to temporary reconnect the
liquid line to the indoor unit's liquid line orifice housing.
506120−01 03/10
STUB END
TXV
TEFLON
RING
TEFLON
RING
SENSING
LINE
LIQUID LINE ASSEMBLY
WITH BRASS NUT
SUCTION
LINE
LIQUID
LINE

Flushing the System

If the original system used:
S
HCFC−22 refrigerant, then flush the system using the
procedure provided in this section.
S
HFC−410A refrigerant, then proceed to Refrigerant
Metering Device Kits.
IMPORTANT
The line set and indoor unit coil must be flushed
with at least the same amount of clean refrigerant
that previously charged the system. Check the
charge in the flushing cylinder before proceeding.
IMPORTANT
If this unit is being matched with an approved line
set or indoor unit coil which was previously
charged with mineral oil, or if it is being matched
with a coil which was manufactured before
January of 1999, the coil and line set must be
flushed prior to installation. Take care to empty all
existing traps. Polyol ester (POE) oils are used in
Lennox units charged with HFC−410A refrigerant.
Residual mineral oil can act as an insulator,
preventing proper heat transfer. It can also clog
the expansion device, and reduce the system
performance and capacity.
Failure to properly flush the system per the
instructions below will void the warranty.
IMPORTANT
The
Environmental
prohibits the intentional venting of HFC refrigerants
during maintenance, service, repair and disposal of
appliance.
Approved
recycling or reclaiming must be followed.
This procedure should not be performed on
systems which contain contaminants (Example:
compressor burn out).
REQUIRED EQUIPMENT
Equipment required to flush the existing line set and indoor
unit coil:
S
Two clean HCFC−22 recovery bottles,
S
Oilless recovery machine with pump-down feature,
S
Two gauge sets (one for HCFC−22; one for
HFC−410A).
Page 12
Protection
Agency
methods
of
CAUTION
(EPA)
recovery,

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents