Fireplace Specifications - Intertherm BM36HC Installation Instructions Manual

36" wood burning fireplaces
Table of Contents

Advertisement

1 ¹⁄₂"
Figure 7
Figure 8
Step 3. Refer to fireplace drawings and speci-
fications on pages 6 and 7 for framing dimen-
sions and details. Frame appliance enclosure as
illustrated in Figures 10 through 13 on page 7.
IMPORTANT: UNDER NO CIRCUMSTANCES
CAN THE FIREPLACE TOP SPACERS ( FIGURE
9 ) BE REMOVED OR MODIFIED, NOR MAY
YOU NOTCH THE HEADER TO FIT AROUND OR
BE INSTALLED LOWER THAN THE SPACERS.
THE HEADER MAY BE IN DIRECT CONTACT
WITH THE TOP SPACERS BUT MAY NOT BE
SUPPORTED BY THEM.
Note: The framed depth, 20 ⁵⁄₈ " (524 mm) from
a framed wall, must always be measured from
a finished surface. If a wall covering such as
drywall is to be attached to the rear wall, then
the 20 ⁵⁄₈ " (524 mm) must be measured from
the drywall surface. It is important that this
dimension be exact.
If the appliance is to be elevated above floor
level, a solid continuous platform must be
constructed.
The header may rest on the top metal spacers,
but must not be notched to fit around them.
Consult all local codes.
6

FIREPLACE SPECIFICATIONS

Metal Safety Strips
Blocking
Metal Safety Strips
Figure 9
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
20 ³⁄₁₆"
(513 mm)
27 ⁷⁄₈"
(708 mm)
3 ⁵⁄₁₆"
(84 mm)
(1067 mm)
Gas Line
Access
(940 mm)
20 ¹⁄₄"
(514 mm)
Left Side
7 ¹³⁄₁₆"
(198 mm)
Appliance
Top Spacer
1"
(25 mm)
36"
(914 mm)
2"
(51 mm)
40"
(1016 mm)
42"
Front
Appliance Top Spacer
Combustion
Air Inlet
37"
9 ³⁄₁₆"
17 ³⁄₈"
(233 mm)
(441 mm)
12 ⁷⁄₈"
(327 mm)
Junction
Box
Right Side
27 ¹⁄₄"
(692 mm)
12 ¹⁄₂"
(318 mm)
40"
(1016 mm)
42"
(1067 mm)
Top View
9 ⁵⁄₈"
(244 mm)
37"
(940 mm)
7 ³⁄₁₆"
(183 mm)
9 ⁷⁄₈"
(251 mm)
32"
(813 mm)
Gas Line
Access
9 ¹⁄₁₆"
(230 mm)
20 ¹⁄₄"
(514 mm)