Savannah Installation and Operation Manual

7.3 Floor protector

If the stove is to be installed on top of a combustible floor, it must be guarded by a non
combustible material as shown on figure 1.3 (see the dotted line area).
G
H
I
J
M
N
*Steel with a minimum thickness of 0.015'' (0.38 mm) or ceramic tiles sealed together
with grout. No protection is required if the unit is installed on a non-combustible floor
(ex: concrete).
Note 1: The floor protection at the back of the stove is limited to the stove's required
clearance if such clearance is smaller than 8 inches (203 mm).
Note 2: Only required under the horizontal section of the connector. Must exceed each
side of the connector by at least 2 inches (51 mm).
32
FLOOR PROTECTOR*
CANADA
8'' (203 mm) – Note 1
8'' (203 mm)
18'' (457 mm)
From door opening
N/A (USA only)
8'' (203 mm)
N/A (USA only)
USA
N/A (Canada only)
N/A (Canada only)
16'' (406 mm)
From door opening
8'' (203 mm)
N/A (Canada only)
Note 2