Heat Controller TGC Series Installation Instructions Manual page 47

Package gas electric
Table of Contents

Advertisement

WARNING
!
DISCONNECT ALL POWER TO UNIT BEFORE SERVICING. CONTACTOR MAY BREAK ONLY ONE SIDE. FAIL-
URE TO SHUT OFF POWER CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
SYMPTOM
Unit will not run
Condenser fan runs, compressor
doesn't
Insufficient cooling
Compressor short cycles
Registers sweat
High head-low vapor pressures
High head-high or normal vapor
pressure - Cooling mode
Low head-high vapor pressures
Low vapor - cool compressor -
iced evaporator coil
High vapor pressure
Fluctuating head & vapor
pressures
Gurgle or pulsing noise at
expansion device or liquid line
Circulating air blower & inducer
run continuously,
compressor will not start
COOLING TROUBLE SHOOTING CHART
POSSIBLE CAUSE
• Power off or loose electrical connection
• Thermostat out of calibration-set too high
• Failed contactor
• Blown fuses
• Transformer defective
• High pressure control open (if provided)
• Interconnecting low voltage wiring damaged
• Run or start capacitor failed (single phase only)
• Start relay defective 9single phase only)
• Loose connection
• Compressor stuck, grounded or open motor winding
open internal overload.
• Low voltage condition
• Low voltage condition
• Improperly sized unit
• Improper airflow
• Incorrect refrigerant charge
• Air, non-condensibles or moisture in system
• Incorrect voltage
• Incorrect voltage
• Defective overload protector
• Refrigerant undercharge
• Low evaporator airflow
• Restriction in liquid line, expansion device or filter drier
• Flow check piston size too small
• Incorrect capillary tubes
• TXV does not open
• Dirty condenser coil
• Refrigerant overcharge
• Condenser fan not running
• Air or non-condensibles in system
• Defective Compressor valves
• Incorrect capillary tubes
• Low evaporator airflow
• Operating below 65°F outdoors
• Moisture in system
• Excessive load
• Defective compressor
• TXV hunting
• Air or non-condensibles in system
• Air or non-condensibles in system
• Manual reset overtemperature control
• tripped
• Wire loose in limit circuit
REMEDY
Check for correct voltage at compressor contactor in control
box
Reset
Check for 24 volts at contactor coil - replace if contacts are
open
Determine cause, remedy, and replace fuses
Check wiring-replace transformer
Reset-also see high head pressure remedy-The high pressure
control opens at 450 PSIG
Replace thermostat wiring
Replace
Replace
Check for correct voltage at compressor -
check & tighten all connections
Wait at least 2 hours for overload to reset.
If still open, replace the compressor.
At compressor terminals, voltage must be within 10% of rating
plate volts when unit is operating.
Add start kit components
Recalculate load
Check - should be approximately 400 CFM per ton.
Charge per procedure attached to unit service panel.
Recover refrigerant, evacuate & recharge, add filter drier
At compressor terminals, voltage must be within 10% of rating
plate volts when unit is operating.
At compressor terminals, voltage must be ± 10% of
nameplate marking when unit is operating.
Replace - check for correct voltage
Add refrigerant
Increase speed of blower or reduce restriction - replace air
filter
Remove or replace defective component
Change to correct size piston
Change coil assembly
Replace TXV
Clean coil
Correct system charge
Repair or replace
Recover refrigerant, evacuate & recharge
Replace compressor
Replace coil assembly
Increase speed of blower or reduce restriction - replace air
filter
Add Low Ambient Kit
Recover refrigerant - evacuate & recharge - add filter drier
Recheck load calculation
Replace
Check TXV bulb clamp - check air distribution on coil - replace
TXV
Recover refrigerant, evacuate & recharge
Recover refrigerant, evacuate & recharge
Reset or replace
Check wiring
47

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents