TABLE OF CONTENTS Unit Features & Benefits ................3-4 General Data TPR Series ....................5 Performance Data TPR Series ................... 6-10 Airflow Performance TPR Series ..................11-12 Electrical Data TPR Series ....................13 Electric Heater Kits ..................14-15 Dimensional Data ..................16-17 Typical Installations ..................18 Accessories ....................19-26...
UNIT FEATURES & BENEFITS—TPR SERIES Features Below Correspond to Photos on Page 3 1. All models feature Copeland ® Scroll ® compressors for 8. Refrigerant connections are conveniently located for maximum efficiency and quiet operation. easy service diagnostics. 2. Louvered condenser compartment for protecting the 9.
ELECTRICAL DATA – TPR SERIES ELECTRICAL DATA TPR24C-1K TPR30C-1K TPR36C-1K TPR42C-1K TPR48C-1K Unit Information Unit Operating Voltage Range 187-253 187-253 187-253 187-253 187-253 Minimum Circuit Ampacity 17/17 21/21 24/24 32/32 37/37 Maximum Overcurrent Protection Device 25/25 30/30 35/35 45/45 50/50...
ELECTRIC HEATER KITS—TPR SERIES Unit Model Application Electric Heater Kit Models RXQJ-A05J (208-240 volt, 1-ph, 5kW) TPR24C-1K RXQJ-A10J (208-240 volt, 1-ph, 10kW) RXQJ-A05J (208-240 volt, 1-ph, 5kW) TPR30C-1K RXQJ-A10J (208-240 volt, 1-ph, 10kW) RXQJ-A10J (208-240 volt, 1-ph, 10kW) TPR36C-1K RXQJ-A15J (208-240 volt, 1-ph, 15kW)
UNIT DIMENSIONS—TPR SERIES UNIT DIMENSIONS SELF-CONTAINED AIR CONDITIONERS OUTDOOR FAN GRILLE AND COMPRESSOR ACCESS CONTROL FILTER ACCESS ACCESS PANEL PANEL (FOR UNIT MOUNTED FILTER ACCESSORY) LIQUID PRESSURE 30% 2% SERVICE PORT OUTDOOR COIL PROTECTIVE GRILLE SUCTION PRESSURE 21% 2% SERVICE PORT THREADED PVC CONDENSATE "...
Page 17
UNIT DIMENSIONS—TPR SERIES SIDE VIEW SIDE VIEW OUTDOOR COIL PROTECTIVE FILTER ACCESS PANEL (FOR UNIT GRILLE THERMOSTAT MOUNTED FILTER ACCESSORY) WIRE ENTRANCE " [28.6 mm] " [643 mm] " [259 mm] " [129 mm] " ELECTRICAL BLOWER/ [1332 mm] "...
Page 21
ACCESSORIES FRESH AIR DAMPER FOR USE ON TPR SERIES RXRF-FAA1 (Fixed - 0-35%) The 0-35% manual outside Air Damper is designed to replace the unit return air duct cover. No drilling or damper assembly is required. The amount of outside air (0-35%) is controlled by sim- ply adjusting the side damper.
Page 22
ACCESSORIES ECONOMIZERS RXRD-CCM10 (Fully Modulating) for TPR Series Horizontal Application RXRD-CCM10 (Fully Modulating) Provided with enthalpy control, mixed air sensor and minimum position poten- tiometer for proportioning (modulating) the amount of fresh air. [ ] Designates Metric Conversions...
Page 23
ACCESSORIES FILTER KIT INSTALLATION RXRY-B01 For use in either vertical or horizontal discharge. CFM [L/s] Airflow Pressure Drop, Inches W.C. [kPa] Minimum Nominal Maximum CFM [L/s] 1" Filter 2" Filter Airflow Airflow Airflow 500 [236] .02 [.0050] .03 [.0075] 510 [241] 600 [283] 660 [311] 600 [283]...
Page 24
ACCESSORIES DUCT ADAPTER SIDEFLOW SQUARE TO ROUND TRANSITION RXMC-BA01 Adapts the side rectangular supply and return openings to 14" [356 mm] diameter round openings. Adapters provided with same finish as unit and also provided with thermal insulation.
Page 25
ACCESSORIES Roofcurb (Sloped) RXQG-AAA14 (14" [356 mm] High) RXQG-AAA14 for TPR Series Heat pump models must use sloped curbs. Hinged corners make for fast, easy set-up. PACKAGE HEAT PUMP ROOFCURB INSTALLATION (Sloped) OUTDOOR FAN GRILLE AND COMPRESSOR ACCESS OUTDOOR COIL...
Page 26
ACCESSORIES LIFT KIT—MODEL NO. RXML-A01 The lift kit is intended for temporary installation while the unit is being lifted into position. Kit includes 4 lift brackets.
Page 28
Design, material, performance data and components subject to change without notice. 1900 Wellworth Ave Jackson, Michigan 49203 • Ph. 517-787-2100 • Fax 517-787-9341 THE QUALITY LEADER IN CONDITIONING AIR www.heatcontroller.com 03/26/07...