Mode 1 & 2: Setpoint Operation: View Display - Camus Hydronics MFH060 Installation, Operation And Service Manual

Modulating micoflame series gas fired residential and commercial copper tube boilers
Table of Contents

Advertisement

18.2
MODE 1 & 2: SETPOINT OPERATION: VIEW DISPLAY
From the Home display;
1) Press [ITEM] to view the following parameters:
Display
Parameter
Name
To provide a target setpoint for the
Boiler Target
heating system. Setpoint is controlled
Temperature
to the inlet sensor
System Temperature of Primary Loop
System
Temperature
NOTE: This parameter is only
available in Mode 2
Boiler Outlet
Real-time Outlet Temperature to Boiler
Temperature
Boiler Inlet
Real-time Inlet Temperature to Boiler
Temperature
Real-time temperature difference
Boiler Delta
between the outlet sensor and the inlet
T
sensor.
Real-time modulating output
Modulation
percentage
Monitors the amount of operational
time since the MicoFlame was
installed. The first two digits are the
Total Run
number of thousands of hours and the
Time Since
three digit display shows the number
Installation
of hundreds of hours.
Press
the counter
30
Parameter Description
simultaneously to reset
Parameter
Range
o
---, 35 to 266
F
o
(---, 2 to 130
C)
o
14 to 266
F
o
(-10 to 130
C)
o
14 to 266
F
o
(-10 to 130
C)
o
14 to 266
F
o
(-10 to 130
C)
o
-99 to 252
F
o
(-72 to 140
C)
0 to 100%
Alternates
between 00 and
999

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents