COa Series 2 Gas-Fired Water Boiler -
Boiler Manual
6a
Start-up - preparation
Checkforgasleaks
IAWARNINGI
IAWARNINGI
28
Before starting
the boiler,
and during
initial
operation,
smell near the
floor
and around the
boiler
for
gas odorant
or any unusual odor. Do
not
proceed
with start-up
if
there
is
any
indication
of
a
gas
leak.
Repair any leak
at
once.
Propane
boilers
only-Your propane
supplier
mixes
an odorant with
the
propane to
make
its
presence detect-
able.
In some
instances,
the odorant
can fade and the gas
may
no longer
have
an
odor.
Propane
gas
can accumulate
at
floor level. Smell
near
the
floor
for the
gas odorant or any
unusual
odor. If
you
suspect a leak,
do not
attempt
to
light
the
pilot.
Periodically
check the
odorant
level
of
your
gas.
Inspect boiler and system at least
yearly
to make
sure all gas
piping
is
leak-tight.
Consult
your
propane supplier
regarding
installation of
a
gas
leak
detector.
There are some products
on
the market
intended for this
purpose. Your supplier
may
be able
to suggest an
appropriate
device.
Detennine if water treatment is needed
IAWARNINGI
Do not
use
petroleum-based cleaning or
sealing
compounds
in
boiler system. Severe damage
to
boiler
will occur, resulting in substantial property
damage.
Eliminate all system leaks. Continual fresh
makeup
water will
reduce
boiler life. Minerals can
build
up in
sections, reducing
heat
transfer,
overheating cast
iron,
and causing section
failure.
Verify water chemistry
Consult
local water treatment
companies
for
unusually
hard
water areas
(above
7 grains hardness) or
low
pH
water
conditions (below
7.0). Boiler
water
pH of7.0 to 8.5 is
recommended.
Freeze protection (when used)
Use
antifreeze made
especially for hydronic systems. Inhibited propylene
glycol
is
recommended.
IAWARNINGI
Do
not
use
ethylene
glycol,
automotive
or undiluted
antifreeze. Severe personal injury or death
can result.
I.
Determine
antifreeze
quantity
according to system water content.
Boiler water
content is
listed
on
page
65.
Remember to
include
e>.-pan-
sion
tank
water content.
2. Follow antifreeze
manufacturer's
instructions.
3.
A 50%
solution
of propylene glycol/water
provides
maximum
protec-
tion to
about
-30°F.
4.
Local codes
may require
baCk
!low
preventer
or actual
disconnect
from
city water
supply.
5.
When using antifreeze
in
a
system
with
automatic
fill,
install
a
water
meter to monitor water makeup. Glycol will leak before
the
water be-
gins to leak, causing glycol
level
to
drop. Added water will dilute
the
antifreeze, reducing
the
freeze
protection
level.
Part