Clearances - Majestic 300DVB User Manual

Dvb direct vent gas fireplace
Table of Contents

Advertisement

cleARANces

cleARANces to coMBustIBles
Follow these instructions carefully to ensure safe installation. Failure
to follow instructions exactly can create a fire hazard.
the appliance cannot be installed on a carpet, tile or other
combustible material other than wood flooring. If installed on carpet
or vinyl flooring, the appliance shall be installed on a metal, wood
or noncombustible material panel extending full width and depth of
the appliance.
71" Minimum
Min. 4" 
From Either 
Side Wall
Figure 4 -
Clearances
Never obstruct or modify the air inlet or
outlet grilles (louvers). this may create a
fire hazard.
54D0701
11" Minimum
FP2248
mantel clearances
12" 
11"
Max.
Top of Exhaust
Louvers
FP48
FP093
Side of Fire-
place Opening
Figure 5 -
Mantel Clearances
DVB Series Direct Vent Gas Fireplace
Wall
12"
8"
6"
2"
7"
5"
3"
side View
FP2204
mantel clearances
Combustible
Material Area
1"
1 "
2 "
3"
4"
top View
FP2093
mantel side clearance
Stud
Insulation
Board
Standoff
FP04
Wall
2 "
45°
9