DETERMINE THE UNIT LOCATION
1.
Locate the appliance so that if water connections should leak, water damage will not
occur. When such locations cannot be avoided, it is recommended that a suitable drain
pan, adequately drained, be installed under the unit. The pan must not restrict
combustion airflow.
Under no circumstances is the manufacturer to be held responsible for water damage in
connection with this unit, or any of its components.
2.
DO NOT install this appliance in any location where gasoline or flammable vapors are
likely to be present.
3.
The appliance must be installed on a level floor. Combustible floor locations may be
used. Maintain required clearances from combustible surfaces.
4.
The appliance must be installed indoors where it is protected from exposure to wind, rain,
and weather.
5.
This appliance may condense the products of combustion if operated at water
temperatures below 140°F (60°C). Ensure that the appliance is located near an
acceptable drain where condensate that may form in the venting system can be properly
collected and disposed.
6.
Access to the rear of the appliance MUST be maintained.
CONDENSATE TRAP
The Power-fin is fitted with a condensate trap to be
field mounted on the floor behind the appliance. The
trap is a requirement of the ANSI standard for any
Category IV vented appliance with condensation
forming in the stack.
CLEARANCES FROM COMBUSTIBLE CONSTRUCTION
Right Side
Zero inches
Left Side
Zero inches
Rear
6" (Minimum 24" suggested for service to
the pump and other components)
Front - Alcove*
(Minimum 24" suggested for service)
Top
6" (Minimum 24" suggested for service)
Flue
2"
Hot Water
Pipes
1"
*An Alcove is a closet without a door.
34
LOCHINVAR CORPORATION
300 MADDOX SIMPSON PKWY
LEBANON, TN 37090
www.lochinvar.com