7845GSM/7845GSMCN Installation and Setup Guide
PROMPTS
Low Bat Rpt Y/N
25
(Y)_
Tamper Rpt Y/N
26
(Y)_
ECP mode supports two optional hardwire zone input triggers by making connections to the module's zone 6 and/or
zone 7 terminals and programming the appropriate zone trigger options below.
Each zone input can be programmed to cause an alarm under one of the following conditions:
• (V+), where a positive voltage causes an alarm for normally low connections (voltage trigger, NO, NC)
• (V–), where a ground trigger causes an alarm for normally high connections (open collector, NO, NC)
• (EOLR) End of Line Resistor, where the input is supervised by a 2K EOL resistor. The zone can be triggered
by open collector, voltage trigger, NO, NC.
In addition to the above, zones can be programmed for an Inverted Trigger, where the alarm and normal states of
the zones are inverted; this can serve a fail-safe supervisory purpose for certain installations.
These zone inputs can also be programmed for restore reporting, and for delayed reporting, which allows time for
the user to abort false alarms.
NOTE: Optional hardwire zones report in ADEMCO High-Speed format.
Enable Zn6 Y/N
27
(N)_
Zn6 Trigger Type
28
(V+)_
Invert Zn6 Y/N
29
(N)_
Restore Zn6 Y/N
30
(Y)_
Delay Zn6 (secs)
31
(00)_
Enable Zn7 Y/N
32
(N)_
Zn7 Trigger Type
33
(V+)_
Invert Zn7 Y/N
34
(N)_
Restore Zn7 Y/N
35
(Y)_
Delay Zn7 (secs)
36
(00)_
3-6
WWW.DIYALARMFORUM.COM
ENTRY
OPTIONS
[Y], [N]
[Y], [N]
Important Information Regarding Zone Input Options
[Y], [N]
• (V+)
• (V–)
• (EOLR)
[Y], [N]
[Y], [N]
[01-15]
[00] = no delay
[Y], [N]
• (V+)
• (V–)
• (EOLR)
[Y], [N]
[Y], [N]
[01-15]
[00] = no delay
WWW.DIYALARMFORUM.COM
DESCRIPTION
Sends a low-battery report when a low battery
condition exists.
UL NOTE: Must be set to "Y" unless used with
LynxR-I series controls. Must be set to "N" when using
LynxR-I series controls.
Sends a tamper report when the module detects a
tamper condition. A tamper restore is automatically
sent when the tamper condition clears.
UL NOTE: Must be set to "Y."
Enables alarm reporting for zone 6.
If [N], skip to Prompt 32: "Enable Zn7."
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
Inverts the alarm and normal states of the zone 6
trigger; otherwise uses normal input signal.
Enables restore reporting for zone 6.
Defines the reporting delay in seconds for zone 6.
Enables alarm reporting for zone 7.
If [N], skip to Prompt 37: "Review."
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
Inverts the alarm and normal states of the zone 7
trigger; otherwise uses normal input signal.
Enables restore reporting for zone 7.
Defines the reporting delay in seconds for zone 7.