The menu is accessed by pressing and holding "SELECT" and "ENTER" buttons for 10 seconds. To access different modes,
press "ENTER" button. To change system setting: Press "UP or DOWN" button, then press "ENTER"
WARNING: Only a trained, experienced service technician or installer should use this table.
MODE DISPLAY
NOTE:
*: Alternating **: Steady
Changing space heating post pump time. Settable from 10 to 900 seconds.
*
Changing DHW post pump time. Settable from 1 to 255 seconds.
*
*
*
*
*
*
*
*
(space heating mode 1 or 2). Settable from 16˚F to 122˚F (steps of 1 F).
Changing compensation slope (space heating mode 1 or 2).
*
*
Changing weather compensation set point (space heating mode 2 only).
*
**
Display shows blower RPM (mutiply reading by 10 for actual RPM)
*
Change blower RPM for high input (steps of 30 RPM, limit +/- 480 RPM).
*
Change blower RPM for low input (steps of 30 RPM, limit +/- 120 RPM).
**
*
Subject to change without notice.
DESCRIPTION
(steps of 10 seconds). The default value is 30 seconds.
(steps of 1 seconds). The default value is 15 seconds.
Changing space heating control mode
0: Thermostat only (default) - boiler without outdoor sensor
1: Outside sensor and Thermostat
2: Outside sensor only
3: Permanent heat demand (boiler circulator always on)
Changing domestic hot water (DHW) mode
0: No DHW
1: Storage tank with sensor
2: Storage tank with thermostat (default value)
3: Plate heat exchanger
Changing DHW or space heating priority mode
0: DHW priority (no time limit)
1: Space heating priority (no time limit)
2: DHW priority for limited time (default)
3: Space heating priority for limited time
Changing priority limited time. Settable from 20 to 80 minutes.
The default value is 30 minutes.
Boiler model selection, value is 1 for model LX-85A
Boiler model confirmation, value is 1 for model LX-85A
Weather compensation supply water reference temperature
The default value is 86˚F.
Settable from 0.1 to 5.0 (steps of 0.1).
The default value is 1.0.
Not Utilized
Settable from 32˚F to 122˚F (steps of 1˚F).
The default value is 68˚F.
Display shows flame current in micro amps
System test – Display shows flame current
0: System test off
L: Steady low input (20 minutes)
I: Steady ignition input (20 minutes)
H: Steady high input (20 minutes)
Table 5