Download Print this page

Slant/Fin Caravan LDZO-1100-3-6 Specification Sheet

Modular boiler submittal data ldzo series—oil-fired/steam
Hide thumbs Also See for Caravan LDZO-1100-3-6:

Advertisement

LDZO SERIES—Oil-Fired/Steam
A Caravan modular boiler system consists of
two or more compact cast-iron boilers that offer
significant advantages in terms of installed
cost, efficiency and reliability. Caravan
systems are based on step-firing just enough
modules to meet space heating demands.
LDZO systems are available in 602,000 to
multi-million Btuh gross input. For additional
information, see Caravan Engineering
Manual, pub. C-30.
Standard Equipment
One per module unless otherwise noted
Pre-assembled cast-iron heat exchanger
with insulated jacket
Flame retention oil burner, with nozzle;
cadmium sulfide flame detector
Primary burner control
System pressure gauge and siphon
(unmounted, one per system)
Module pressure gauge and siphon
(unmounted)
Module pressure relief valve (ASME)
(unmounted) 15 PSI.
Draft regulator (unmounted)
Flue brush
Ratings
Oil Caravan ratings and dimensions/steam models — LDZO Series
No. of
Heating
Modules
Model No.
LDZO-600-2-5
2
LDZO-750-2-6
2
LDZO-850-2-7
2
LDZO-900-3-5
3
LDZO-1100-3-6
3
LDZO-1300-3-7
3
LDZO-1700-4-7
4
LDZO-2100-5-7
5
* Light oil, 140,000 Btu. per gallon.
† Net ratings are based on piping and pick-up allowance of 1.33.
Slant/Fin should be consulted before selecting a boiler for
installation having unusual piping and/or pick-up requirements.
For higher elevations, input may need to be reduced
Modular Boiler Submittal Data
®
Module drain cock
(unmounted)
Water level sight glass
(unmounted)
Ratings for No. 2 Oil
I=B=R
Burner
Gross
Capacity
Output
Input
Efficiency
(GPH)*
(MBH)
MBH
4.3
602
500
5.2
728
596
6.0
840
684
6.4
896
750
7.8
1092
894
9.0
1260
1026
12.0
1680
1368
15.0
2100
1710
ASME Required Options
67 Low water cut off (one per module)
PA404A Pressure control (one per module)
67M Low water cut off (one per system)
L4079B Manual reset pressure control
Net
Comb.
Sq.Ft
Output
Steam‡
MBH†
85.90
375
1563
85.80
447
1863
85.50
513
2138
85.90
563
2345
85.80
671
2796
85.50
770
3208
85.50
1035
4313
85.50
1319
5496
‡ Based on 240 Btuh per square foot E.D.R. at 215˚F average
steam temperature.
Modules in excess of 5 are piped in parallel in two or more
banks.
(one per system)
Boiler
Weight
Water
Horse-
with
Content
power
Water
(gal)
14.9
21.4
1426
17.8
25.2
1630
20.4
29.0
1838
22.4
32.1
2139
26.7
37.8
2445
30.6
43.5
2756
40.9
58.0
3675
51.1
72.5
4594
Recom-
mended
Header
Size
3"
3"
3"
3"
5"
5"
6"
6"

Advertisement

loading

Summary of Contents for Slant/Fin Caravan LDZO-1100-3-6

  • Page 1 (unmounted, one per system) Module pressure gauge and siphon (unmounted) Module pressure relief valve (ASME) (unmounted) 15 PSI. Draft regulator (unmounted) Flue brush Ratings Oil Caravan ratings and dimensions/steam models — LDZO Series Burner No. of Capacity Heating (GPH)* Modules Model No.