Quadra-Fire Village QV36D-A Installer's Manual page 14

Village collection direct vent gas fireplace heater
Table of Contents

Advertisement

VENTING WITH TWO (2)
90° ELBOWS
V
H
1´ MIN. (305 mm)
2´ MAX. (610 mm)
2´ MIN. (610 mm)
4´ MAX. (1.22 m)
3´ MIN. (914 mm)
6´ MAX. (1.86 m)
4´ MIN. (1.22 m)
8´ MAX. (2.48 m)
V+H+H
= 40´ MAX. (12.4 m) H = 8´ MAX. (2.48 m)
1
Figure 14. Venting with Two 90° Elbows
VENTING WITH TWO (2) 90
V FT.
1' MIN. (305mm)
2' MIN. (610mm)
3' MIN. (914mm)
4' MIN. (1.22m)
V+H+H
= 40' MAX.(12.4m)
1
V+V
+H = 40' MAX.(12.4m)
1
H
1
NOTE: There MUST be a 25% reduction in total
H when using flex vent except when using the
simple up and out installation (see Figure 6).
Figure 15. Venting with Two 90° Elbows
H
1
H + H
1
5´ MAX. (1.52m)
10´ MAX. (3.1m)
15´ MAX. (4.65m)
20´ MAX. (6.2m)
H+H
= 20´ MAX. (6.2m)
1
o
ELBOWS
H + H
(FT.)
1
5´ MAX. (1.52m)
10´ MAX. (3.1m)
15´ MAX. (4.65m)
20´ MAX. (6.2m)
H+H
= 20´ MAX. (6.2m)
1
H
16
V
H
NOTE: There MUST be a 25% reduction in total
H when using flex vent except when using the
simple up and out installation (see Figure 6).
H
V
1
V
V