Minimum Clearances To Combustibles - Regency Plateau PTO30CFT-1 Owners & Installation Manual

Plateau series outdoor decorative gas appliances
Table of Contents

Advertisement

The clearances listed below are Minimum distances unless otherwise stated:
A major cause of fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this
decorative gas appliance be installed only in accordance with these instructions.
Caution Requirements
The top, back and sides of the decorative gas appliance
are defi ned by standoffs. The metal ends of the
standoff may NOT be recessed into combustible
construction.
Regency Plateau
®
Series Outdoor Gas Fireplace

MINIMUM CLEARANCES TO COMBUSTIBLES

Plateau® Series Clearance Requirements
Clearance:
Dimension
A: Back wall
17" (432mm)
B: Sidewall
17" (432mm)
C: Ceiling
45" (1143mm)
D
1
: Floor
D
2
: Floor
E: Alcove Width
84"(2134mm)
F: Alcove Depth
60" (1524mm)
Notes:
A
F
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this decorative gas
appliance be installed only in accordance with these instructions.
Burner to back wall
Burner to sidewall
Burner to Ceiling
0"
When using supplied leveling legs or optional casters.
1"(25mm)
Unit Base to Floor
Wall to Wall (Minimum)
Front to Back Wall (Maximum)
0"
No Hearth Required
C
B
D
E
Alcove
INSTALLATION
WARNING
Fire hazard is an extreme risk
Measured From:
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Plateau pto30ist-1Plateau pto30ckt-1

Table of Contents