STA-RITE 200K BTU/HR Owner's Manual page 24

Sr pool and spa heater natural gas / lp gas; 200k btu/hr; 333k btu/hr; 400k btu/hr
Hide thumbs Also See for 200K BTU/HR:
Table of Contents

Advertisement

Heater Will Not Fire - B
Start
Is red "SERVICE
HEATER" LED "on"
YES
CONTINUE
NO
Is red "SERVICE SYSTEM"
LED on?
Verify that pump is on, filter is
not blocked, and the water
flow is above the minimum
requirement.
With pump running, adjust
Water Pressure Switch to
lower pressure until 'SER-
VICE SYSTEM" LED goes
out. Then verify that "SER-
VICE SYSTEM" LED goes on
with pump off.
Check that water pressure is
within the adjustment range of
the Pressure Switch (0-5 psig)
Verify that switch wiring is OK
and sensing tube is not
blocked, and replace water
Pressure Switch.
Check whether any of the
red diagnostic LED's (AGS,
AFS, ES2, HLS or PS) are
"on"
GO TO
"HEATER WILL NOT FIRE - C"
Page 25
NO
YES
NO
YES
YES
NO
NO
YES
YES
NO
24
Increase POOL/SPA tempera-
ture setting on Membrane
Pad above actual water tem-
perature. Heater should fire
on demand for heat. If not,
and no other red LED's light,
replace Control Board.
Service pump/filter and elimi-
nate other flow obstructions.
Heater should fire on call for
heat. Re-verify that water flow
is above minimum require-
ment by checking tempera-
ture rise across heater.
Maximum/Minimum Temperature
Rise Through Heater
Max. Temp. Min. Temp.
Model
Rise
200
17°F
333
18°F
400
17°F
If water pressure is outside of
adjustment range that will
open switch with pump off
and close switch with pump
on, replace with flow switch
set above minimum flow
requirement.
Minimum Flow Requirements
Model
Flow
200
20 GPM
333
30 GPM
400
40 GPM
Go to "Diagnostic LED's",
(Page 27)
Rise
3°F
5°F
6°F

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents