• at least 4 feet below or horizontally from, or 1 foot
above, any doors or windows or gravity air inlet to a
building
• At least 3 feet above any forced air inlet located within
10 feet
• At least 4 feet horizontally from electric meters, gas
meters, regulators and relief equipment
• At least 7 feet above grade adjacent to walkways or sim-
ilar traffic areas.
Allow at least 3 feet vertical clearance over vent termina-
tion when terminating under an overhang or deck.
Avoid corners or alcoves where snow or wind could have
an effect. Exhaust may affect shrubbery and some building
materials. Keep shrubbery away from termination. To pre-
vent staining or deterioration, sealing or shielding exposed
surfaces may be required.
Support
weight
of pipe
Metal Special
Gas Vent
requires
Appliance
Adapter
Metal
Vent
Body
2787 0297
FIGURE 14: Typical Special Gas Vent Pipe Installation
(Horizontal-Positive Pressure)
Table 7: Listed Thimbles and Vent Terminals (for Special Gas Vents)
Vent Brand
Saf-T Vent
®
Saf-T CI Vent
®
Z-Vent
Listed
Terminal
Slope at least
1/4" per foot
down towards
3" Minimum,
condensate drain
12" Maximum
Clearance
Condensate drain
w/Trap
Wall Thimble
(Part of Vent term.)
(Part of Vent term.)
SVSWTX04
8.
Fire Hazard. Do not run the heater vent
into a common vent with any other appliance. Do not
run the Special Gas Vent into, through, or within any
active vent such as a factory built or masonry chimney.
Table 6: Maximum Vent Length
4" Special Gas Vent (Vertical or Horizontal)*
No. of 90° Elbows
0
2
4
6
* Minimum vent length is three (3) feet.
Final Installation Check:
Check that horizontal vent pipe runs slope uniformly at
least 1/4" per foot to condensate drain(s). No sags, no dips,
no high or low spots.
Check that vent is supported at elbows, tees, and horizon-
tal and vertical runs according to manufacturer's instruc-
tions and code requirements.
Check that vent supports and wall and ceiling penetrations
allow free movements up, down, and sideways without
putting any strains on the heater or vent body.
Check for at least six (6) inch free air clearance between
the heater vent pipe and combustible materials.
Check that all joints are completely together and sealed.
Horizontal Terminal
5490CI Horizontal Term.
5490CI Horizontal Term.
SVETTX04 Tee
15
Maximum Length
50 Ft.
40 Ft.
30 Ft.
20 Ft.
Vertical Terminal
5400 Cap
5400 Cap
SVERCX04 Cap