7. High pressure overhigh protection: 13 flashes of outdoor alarm lamp.
When high pressure switch is activated: Pressure is above 3.0 MPa.
Are connectors of CN16 pressure switch
in good condition?
Is high pressure switch activated?
Is pressure value detected by
pressure gage above 3MPa?
Are stop valves in suction
pipe and liquid pipe of
outdoor unit open?
Is piping twisted or deformed?
if outdoor fan motor work properly during cooling
cycle? and if indoor fan motor and indoor EEV
work properly during heating cycle?
Is filter or heat exchanger dirty?
Is system overfed? Is there air in system?
Is reading of discharging pipe pressure
gauge oscillatory?
Evacuate and recharge
no
Check and reconnect
yes
no
replace PCB
yes
no
Replace high side pressure switch
yes
no
Open stop valve
yes
yes
Repair or
replacement
no
no
yes
yes
cleaning
no
yes
>a__WcU[S^ <[c >a`V[e[a`Wc
Check fan motor
or indoor EEV
-175-