Heat Pump - Carrier 38YY...G Installation Manual

R-410a
Hide thumbs Also See for 38YY...G:
Table of Contents

Advertisement

38YY...G / 38YYS...G
Refrigerant connections
Three-way valve (Gas)
Needle valve
Valve cap
Valve needle
Two-way valve (Liquid)
Allen (hex. head) wrench
Air purging
Use only a vacuum pump to purge air from the piping.
NEVER use the system compressor as a vacuum pump.
NEVER use the unit refrigerant gas to purge the connecting
pipes.
No additional refrigerant has been provided in the unit for this
purpose.
Remove the caps from the two and three-way valves.
Create a vacuum with a vacuum pump connected to the service
connection of the suction shut-off valve, as shown, keeping the
shut-off valves completely shut until a 50 Pa (0.5 mbar) vacuum
has been reached.
Now open the two-way valve for 3 sec., then quickly shut it to
check for possible leaks.
After the leak check, fully open the two and three-way valves.
Replace caps and check for leaks.
Table III: Operating limits
Cooling (2)
Heating (3)
Mains power supply
Notes:
1. Data referred to the outdoor unit only.
2. According to ISO 5151.2/T1.
3. According to ISO 5151.2/High+.
d.b. - dry bulb w.b. - wet bulb
GB - 8
R-410A
Gas line (large diameter)
Liquid line (small diameter)
Flare nut
Indoor unit
Outdoor unit
Vacuum pump
(1)
Maximum conditions
Minimum conditions
Maximum conditions
Minimum conditions
Nominal single-phase voltage
Operating voltage limits
Once all connections have been completed, check for leaks by
using a leak detector specific for HFC refrigerants.
Finally wrap the valves and pipes with anti-condensate insulation
and tighten this with tape, without exerting too much pressure on
the insulation.
Repair and cover any possible cracks in the insulation.
Fix the pipes to the wall with hooks or conduits.
outdoor temperature 43°C
indoor temperature 32°C d.b.; 23°C w.b.
outdoor temperature 15°C
indoor temperature 21°C d.b.; 15°C w.b.
outdoor temperature 24°C d.b.; 18°C w.b.
indoor temperature 27°C d.b.
outdoor temperature –15°C d.b.; –17°C w.b.
230V ~ 50Hz
min. 198V – max. 264V
WARNING:
During heat pump operation unit will undergo several defrost cycles to
eliminate ice that might possibly collect on the outdoor unit in very low
ambient temperatures.
In these cycles, fan speed will automatically reduce and cannot be
varied until defrost cycle is completed.