Clearances
A minimum of 2" circumferential
clearance from non-insulated hot water
pipes to combustible construction must
be maintained. In cases where the pipes
are insulated with pipe insulation of
appropriate and sufficient thickness and
insulation values, the above clearance
may be reduced to 0".
Waterside flow
20 50
16 40
12 30
8 20
4 10
3.2
8
2
5
1.6
4
1.2
3
0.8
2
0.4
1
0.5
1
2.2
4.4
Waterflow
VR1-22 to -33
Flow rates
The relationship between boiler flow rate and temperature rise is according
to the formula:
Boiler output (Btu/h) = 500 x flow (USGPM) x Rise (°F)
The following chart lists typical flow rates for the Vitorond boiler:
VR1
Boiler Model
20°F rise
USGPM
30°F rise
USGPM
3
2
3
4
5
6
7
m
/h
9
13
18
22
26
31
USGPM
-22
-27
-33
8
9.2
12.2
5.3
6.1
8.1