Bosch C 1210 ES Installation Manual page 49

Bosch indoor residential and commercial models tankless water heaters temperature modulated with electronic ignition suitable for heating potable water and space heating, natural & liquefied petroleum (lp) gas
Table of Contents

Advertisement

specifications in Section 3.4, page 24 Combustion
Air Requirements.
4. Cross contamination. Ensure that intake and exhaust
terminations maintain required clearances as stated
in chapter 3.3, page 10. Cross contamination
between intake and exhaust may cause unstable
burner flames and noise.
5. Lack of gas pressure. Inadequate gas pressure will
cause the fuel-to-air mixture (CO
adjustment. This will result in unstable burner flames
and noise. Ensure gas pressure is in accordance with
specifications in Section 3.14, page 35 Measuring
Gas Pressure. A gas pressure reading is needed to
proceed further. Contact your original installer or a
local certified gas technician to obtain this reading.
6. Verify proper CO
readings per chapter 6.5, page
2
42. CO
adjustments must be done by a certified
2
gas technician with a calibrated combustion gas
analyzer.
6 720 644 887
) to be out of
2
Troubleshooting
49