Model number nomenclature
LEGEND
Al
— Aluminum
Cu
— Copper
*Refer to 50TFQ Product Ordering Data or contact your local Carrier rep-
resentative for 50TFQ Factory-Installed Option code table.
Ratings summary
UNIT
NOMINAL
50TFQ
kW
008
26.4
009
29.9
012
35.2
LEGEND
— Bypass Factor
BF
db
— dry bulb
MBtuh — Btuh x 1000
wb
— wet bulb
NOTE: Ratings are net values adjusted for the effects of indoor-fan motor heat. Ratings are based on:
Cooling Standard: 27 C (80 F) db, 19 C (67 F) wb indoor entering-air temperature and 35 C
(95 F) db outdoor entering-air temperature.
High-Temp Heating Standard: 21 C (70 F) db indoor entering-air temperature and 8 C (47 F)
db, 6 C (43 F) wb outdoor entering-air temperature.
Low-Temp Heating Standard: 21 C (70 F) db indoor entering-air temperature and –8 C (17 F)
db, –9 C (15 F) wb outdoor entering-air temperature.
AIRFLOW QUANTITIES
(Nominal)
NOMINAL
TONS
L/s
7.5
1200
8.5
1400
10
1600
Cooling
Cfm
kW
MBtuh
2600
21.3
73.0
3000
23.4
80.0
3400
26.9
92.0
NET CAPACITIES
Heating
High
Kw
MBtuh
kW
19.3
66.0
8.7
21.6
74.0
10.8
24.3
83.0
12.8
Low
MBtuh
30.0
37.0
44.0
3