Provide Clearances; Rig And Place Unit - Carrier 48DU Installation Instructions Manual

Infinity 14 single-packaged air conditioner and gas furnace system with puron (r-410a) refrigerant 2 to 5 nominal tons (sizes 024-060)
Hide thumbs Also See for 48DU:
Table of Contents

Advertisement

UNIT SIZE
NOMINAL CAPACITY (ton)
OPERATING WEIGHT (lb.)
COMPRESSORS
Quantity
REFRIGERANT: PURON (R- - 410A)
Quantity (lb.)
REFRIGERANT METERING DEVICE
Size
Part Number
OUTDOOR FAN
Nominal Cfm
Diameter (in.)
Motor Hp (Rpm)
OUTDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
INDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
INDOOR FAN
Nominal Airflow (Cfm)
Comfort
Efficiency
Max
Furnace (gas ht.) airflow --- Low Stage
Furnace (gas ht.) airflow --- High Stage
Size (In.)
Motor HP (RPM)
FURNACE SECTION*
Burner Orifice No. (Qty...Drill Size)
Natural Gas
HIGH- - PRESSURE SWITCH (psig)
Cut- -out
Reset (Auto)
HIGH- - PRESSURE SWITCH 2 (psig)
(Compressor Solenoid)
Cut- -out
Reset (Auto)
LOSS- - OF- - CHARGE /
LOW- - PRESSURE SWITCH
(Liquid Line) (psig)
Cut- -out
Reset (auto)
RETURN- - AIR FILTERS (in.)†
Throwaway
*Based on altitude of 0 to 2000 ft.
{Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/min-
ute for throwaway type or 450 ft/minute for high- -capacity type. Air filter pressure drop for non- -standard filters must not exceed 0.08 in. wg.
Step 3—Provide Clearances
The required minimum service clearances are shown in Fig. 5 and
6. Adequate ventilation and outdoor air must be provided. The
outdoor fan draws air through the outdoor coil and discharges it
through the top fan grille. Be sure that the fan discharge does not
recirculate to the outdoor coil. Do not locate the unit in either a
corner or under an overhead obstruction. The minimum clearance
under a partial overhang (such as a normal house overhang) is 48 in.
above the unit top. The maximum horizontal extension of a partial
overhang must not exceed 48 in.
IMPORTANT: Do not restrict outdoor airflow. An air restriction at
either the outdoor- -air inlet or the fan discharge may be detrimental
to compressor life.
Do not place the unit where water, ice, or snow from an overhang
or roof will damage or flood the unit. Do not install the unit on
carpeting or other combustible materials. Slab- -mounted units
should be at least 4 in. above the highest expected water and runoff
levels. Do not use unit if it has been under water.
Table 1—Physical Data (Con't) - - Unit 48DU
048090
048115
4
4
521
521
15.3
15.3
4 Ton
4 Ton
EA36YD149
EA36YD149
3300
3300
22
22
1/4 (1100)
1/4 (1100)
2...21
2...21
19.4
19.4
3...17
3...17
5.7
5.7
Variable based on Comfort Roll back (see User Interface instructions for more information).
1400
1400
1600
1600
815
1215
1385
1885
11x10
11x10
3/4
3/4
3...38
3...33
24x36x1
24x36x1
7
048130
060090
4
5
521
572
2- -Stage Scroll
1
15.3
15.8
TXV
4 Ton
5 Ton
EA36YD149
EA36YD159
3300
3300
22
22
1/4 (1100)
1/3 (1110)
2...21
2...21
19.4
23.3
3...17
4...17
5.7
5.7
1400
1750
1600
2000
1255
845
1875
1300
11x10
11x10
3/4
1
3...31
3...38
670
10
±
470
25
±
565
15
±
455
15
±
25
5
±
55
5
±
24x36x1
24x36x1
Step 4—Rig and Place Unit
Rigging and handling of this equipment can be hazardous for many
reasons due to the installation location (roofs, elevated structures,
etc.).
Only trained, qualified crane operators and ground support staff
should handle and install this equipment.
When working with this equipment, observe precautions in the
literature, on tags, stickers, and labels attached to the equipment, and
any other safety precautions that might apply.
Training for operators of the lifting equipment should include, but
not be limited to, the following:
1. Application of the lifter to the load, and adjustment of the
lifts to adapt to various sizes or kinds of loads.
2. Instruction in any special operation or precaution.
3. Condition of the load as it relates to operation of the lifting
kit, such as balance, temperature, etc.
Follow all applicable safety codes. Wear safety shoes and work
gloves.
060115
060130
5
5
572
572
15.8
15.8
5 Ton
5 Ton
EA36YD159
EA36YD159
3300
3300
22
22
1/3 (1110)
1/3 (1110)
2...21
2...21
23.3
23.3
4...17
4...17
5.7
5.7
1750
1750
2000
2000
1215
1255
1910
1920
11x10
11x10
1
1
3...33
3...31
24x36x1
24x36x1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents