Carrier 48DU Installation Instructions Manual page 23

Infinity 14 single-packaged air conditioner and gas furnace system with puron (r-410a) refrigerant 2 to 5 nominal tons (sizes 024-060)
Hide thumbs Also See for 48DU:
Table of Contents

Advertisement

a. Furnace must operate within rise range listed on rating
plate.
b. Select "COMFORT" or "EFFICIENCY" mode on UI.
"COMFORT" mode will provide a warmer supply air
temperature, while "EFFICIENCY" will provide lower
gas consumption.
c. Make sure access panel is re- -installed on the unit.
d. Measure supply and return temperatures as close to the
unit as possible. Subtract the return temperature from the
supply temperature to determine rise. Rise should fall
within the range specified on the rating plate.
5. Adjust manifold pressure to obtain high stage input rate (See
Fig. 18).
a. Set unit to run for 20 minutes in high- -stage gas heat
operation using the "INSTALLER CHECKOUT" menu
on the UI.
b. Remove regulator adjustment cap from high stage gas
valve pressure regulator (See Fig. 18) and turn high- -stage
adjusting screw (3/16 or smaller flat- -tipped screwdriver)
counterclockwise (out) to decrease rate and clockwise
(in) to increase input rate.
NOTE: DO NOT set high stage manifold pressure less than 3.2 in
wc or more than 3.8 in wc for natural gas. If manifold pressure is
outside this range, change main burner orifices.
c. Re- -install high stage regulator adjustment cap.
d. Leave manometer connected.
6. Verify natural gas high stage input rate.
a. Turn off all other gas appliances and pilots served by the
gas meter.
b. If unit is not running, set unit to run for 20 minutes in high
stage gas heat operation using the "INSTALLER
CHECKOUT" menu on the UI.
c. Record number of seconds for gas meter to complete 1
revolution.
d. Divide number of seconds in step c. into 3600 (number
of seconds in 1 hour).
e. Multiply result of step d. by the number of cubic feet
shown for one revolution of test dial to obtain cubic feet
of gas flow per hour.
f. Multiply result of step f. by Btu heating value of the gas
to obtain total measured input shown in Table 4. (Consult
the local gas supplier if the heating value of gas is not
known).
EXAMPLE: Assume a 90,000 high stage input unit is being
installed. Assume that the size of the dial is 2 cubic ft., one
revolution takes 84 sec., and the heating value of the gas is 1050
Btu/ft3. Proceed as follows:
a. 84 sec. to complete one revolution
b. 3600/84 = 42.9
c. 42.9 x 2 = 85.8 ft3 of gas flow/hr.
d. 85.8 x 1050 = 90,090 Btuh input.
In this example, the nominal input rate for high stage is 90,000
Btu/hr, so the high stage manifold pressure is correctly set.
If the measured high stage rate is too low, increase the manifold
pressure to increase rate. If the measured high stage rate is too high,
decrease the manifold pressure to decrease rate.
NOTE:Double- -check that User Interface is running on high stage
gas heat while clocking the low stage firing rate.
7. Verify proper high stage gas heat temperature rise.
a. Furnace must operate within rise range listed on rating
plate.
b. Make sure access panel is re- -installed on the unit.
c. Measure supply and return temperatures as close to the
unit as possible. Subtract the return temperature from the
supply temperature to determine rise. Rise should fall
within the range specified on the rating plate.
NOTE: If the temperature rise is outside the rating plate range, first
check:
a. Gas input for low and high stage gas heat operation.
b. Derate for altitude, if applicable.
c. Return and supply ducts for excessive restrictions
causing static pressures in excess of .5 in. wc.
d. Make sure model plug is installed.
8. Final Check
a. Turn off gas to unit
b. Remove manometer from pressure tap.
c. Replace pipe plug on manifold (See Fig. 19).
d. Turn on gas to unit.
e. Check for leaks.
CHECK GAS INPUT (PROPANE GAS)
Refer to propane kit installation instructions for properly checking
gas input.
NOTE: For installations below 2,000 ft., refer to the unit rating plate
for proper propane conversion kit. For installations above 2,000 ft,
contact your distributor for proper propane conversion kit.
CHECK BURNER FLAME
With burner access panel removed, observe the unit heating
operation. Watch the burner flames to see if they are light blue and
soft in appearance, and that the flames are approximately the same
for each burner. Propane will have blue flame (See Fig. 20). Refer
to the Maintenance section for information on burner removal.
MANIFOLD
Fig. 19 - - Burner Assembly
23
PIPE PLUG
C99019

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents