As for fiber out of the cabinet, make sure to protect the fiber
against any damages with plastic corrugated sleeve. The fiber
within the protect sleeve must not be wound up and the corners
must be radian. The labels at two ends of the fiber must be clear.
The meaning of the label must correctly reflect corresponding se-
rial numbers and relationship between cabinets and between rows.

Power-on Procedures

Check environment in lab and hardware installation before
power-on ZXR10 5900E.
1. Check whether lab temperature, humidity and voltage meet
the installation requirements, as shown in
T
14 T
ABLE
EMPERATURE AND
Temperature (℃)
I-
t-
Long-Term
e-
Working
m
Condition
(Note 1)
S-
c-
o-
15℃~30℃
p-
e
1.
When ZXR10 5900E works in normal environment, temperature and
humidity measurement points refer to values measured at points 2m
above the floor and 0.4m in front of equipment (they must be measured
when there is no protection plate in front and back of cabinet).
2.
Short-term working conditions refer to less than 48 continuous hours
and less than 15 accumulated days per year.
2. Check if power cable and other cables are connected correctly
and reliably.
3. Check other hardware.
i. Check if devices are labeled completely, correctly and
clearly.
ii. Check if switch is firmly installed in 19-inch standard rack
or if it is stably installed on desktop.
iii. Check if power switch of switch is at off position.
iv. Check if rack has a good contact and if earthing resistance
meets technical requirements.
4. Power on ZXR10 5900E in the following steps:
i. Connect switch AC power cable.
Switch End
Connector Type
H
UMIDITY
Relative Humidity (%)
Short-Term
Long-Term
Working
Working
Condition
Condition
(Note 2)
-5℃~45℃
30%~70%
Opposite End
Connector Type
ST/PC Connector
Table
14.
Short-Term
Working
Condition
20%~90%