Upright Installations; Orizontal Nstallations; Startup Procedure & Adjustment; Urnace Operation - Goodman GMH95 Installation Instructions Manual

Gas-fired warm air furnace
Hide thumbs Also See for GMH95:
Table of Contents

Advertisement

COO LING AIRFLO W REQ UIREM ENT (CFM )
600
0453BXA
194*
0703BXA
---
0704CXA
---
0904CXA
---
0905DXA
---
1155DXA
---
*Minimum filter area dictated by heating airflow requirement.
Permanent Minimum Filter Area (sq. in)
[Based on a 600 ft/min filter face velocity]
COOLING AIRFLOW REQUIREMENT (CFM)
600
0453BXA
388*
0703BXA
---
0704CXA
---
0904CXA
---
0905DXA
---
1155DXA
---
*Minimum filter area dictated by heating airflow requirement.
Disposable Minimum Filter area (sq. in)
[Based on 300 ft/min filter face velocity]
U
I
PRIGHT
NSTALLATIONS
Depending on the installation and/or customer preference, differ-
ing filter arrangements can be applied. Filters can be installed in
the central return register or a side panel external filter rack kit
(upflows). As an alternative a media air filter or electronic air cleaner
can be used as the requested filter.
The following figure shows possible filter locations.
AIR FLOW
CENTRAL
RETURN
GRILLE
SIDE RETURN
EXTERNAL FILTER
RACK KIT
(EITHER SIDE)
Possible Upright Upflow
Filter Locations
NOTE: Internal filter retention is not provided on this furnace. If an
internal installation is desired, an internal filter retention kit is avail-
able as an accessory. Please see your distributor for details.
800
1000
1200
1400
1600
194*
240
288
---
---
324*
324*
324*
336
---
---
291*
291*
336
384
---
432*
432*
432*
432*
---
---
388*
388*
388*
---
---
486*
486*
486*
800
1000
1200
1400
1600
388*
480
576
---
---
647*
647*
647*
672
---
---
583*
583*
672
768
---
863*
863*
863*
863*
---
---
777*
777*
777*
---
---
971*
971*
971*
FILTER
ACCESS
DOOR
RETURN
DUCT
FILTER
SUPPORT
BRACKET
(PROVIDED)
AIR FLOW
Possible Upright Counterflow
H
I
ORIZONTAL
Filters must be installed in either the central return register or in the
2000
return air duct work.
---
XIV. STARTUP PROCEDURE & ADJUSTMENT
---
Furnace must have a 115 VAC power supply properly connected
---
and grounded. Proper polarity must be maintained for correct op-
---
eration. In addition to the following start-up and adjustment items,
refer to further information in Section XVI, Operational Checks.
480
486*
H
A
EAT
NTICIPATOR
The heat anticipator in the room thermostat must be correctly ad-
justed to obtain the proper number of cycles per hour and to pre-
vent "overshooting" of the setting. Set the heat anticipator setting to
0.7 amps. Follow the thermostat manufacturer's instructions on
how to adjust the heat anticipator setting.
D
T
RAIN
RAP
2000
The drain trap must be primed prior to furnace startup. To prime, fill
---
the drain trap with water. This ensures proper furnace drainage
---
upon startup and prohibits the possibility of flue gases escaping
through the drain system.
---
F

URNACE OPERATION

---
Purge gas lines of air prior to startup. Be sure not to purge lines
960
into an enclosed burner compartment.
971*
Check for leaks using an approved chloride-free soap and water
solution, an electronic combustible gas detector, or other approved
method. Verify that all required kits (propane gas, high altitude,
etc.) have been appropriately installed.
F
S
URNACE
TARTUP
1. Close the manual gas shutoff valve external to the furnace.
2. Turn off the electrical power to the furnace.
3. Set the room thermostat to the lowest possible setting.
4. Remove the burner compartment door.
NOTE: This furnace is equipped with an ignition device which
automatically lights the burner. Do not try to light the burner by
hand.
5. Move the furnace gas valve manual control to the OFF
position.
6. Wait five minutes then smell for gas. Be sure to check near
the floor as some types of gas are heavier than air.
CENTRAL
7. If you smell gas after five minutes, immediately follow the
RETURN
instructions on page 4 of this manual. If you do not smell
GRILLE
gas after five minutes, move the furnace gas valve manual
control to the ON position.
8. Replace the burner compartment door.
9. Open the manual gas shutoff valve external to the furnace.
10. Turn on the electrical power to the furnace.
11. Adjust the thermostat to a setting above room temperature.
12. After the burners are lit, set the thermostat to desired
temperature.
F
S
URNACE
HUTDOWN
1. Set the thermostat to the lowest setting. The integrated
control will close the gas valve and extinguish flame.
Following a 15 second delay, the induced draft blower will
be de-energized. After a 100 or 150 second delay period
(field selectable), the circulator blower will be de-energized.
2. Remove the burner compartment door and move the furnace
gas valve manual control to the OFF position.
3. Close the manual gas shutoff valve external to the furnace.
4. Replace the burner compartment door.
27
NSTALLATIONS
S
ETTING
P
RIMING

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gch9

Table of Contents