Air-Conditioners PUHZ-RP·HA-A INSTALLATION MANUAL FOR INSTALLER English For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
If the unit is mounted on an unstable structure, it may fall down and cause • Use only accessories authorized by Mitsubishi Electric and ask a dealer or damage or injuries.
1. Safety precautions 1.3. Before electric work Caution: • Be sure to install circuit breakers. If not installed, electric shock may result. • Be sure to ground the unit. Do not connect the ground wire to gas or water • For the power lines, use standard cables of sufficient capacity. Otherwise, a pipes, lighting rods, or telephone grounding lines.
2. Installation location 2.4.2. When installing a single outdoor unit (Refer to the last page) Minimum dimensions are as follows, except for Max., meaning Maximum dimensions, indicated. The figure in parentheses are for RP4-6 models. Refer to the figures for each case. 1 Obstacles at rear only (Fig.
4. Installing the refrigerant piping 4.1. Precautions for devices that use R410A refrigerant • Refer to page 3 for precautions not included below on using air conditioners with R410A refrigerant. • Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil applied to the flared sections.
Page 6
4. Installing the refrigerant piping 4.3. Refrigerant piping (Fig. 4-3) Remove the service panel D (three screws) and the front piping cover A (two screws) and rear piping cover B (two screws). 1 Perform refrigerant piping connections for the indoor/outdoor unit when the out- door unit’s stop valve is completely closed.
4. Installing the refrigerant piping 4.7. Precautions when reusing existing R22 refrigerant pipes • Refer to the flowchart below to determine if the existing pipes can be used and if it is necessary to use a filter dryer. • See below for oil condition. Clear to slight yellow color →...
6. Electrical work 6.1. Precautions (Fig. 6-1) • The compressor will not operate unless the power supply phase connection is cor- rect. • Grounding protection with a no-fuse breaker (earth leakage breaker [ELB]) is usu- ally installed for D. • The connection wiring between the outdoor and indoor units can be extended up to a maximum of 50 meters, and the total extension including the crossover wiring between rooms is a maximum of 80 m.
7. Test run 7.2. Unit replacement operation s When reusing existing pipes that carried R22 refrigerant, replacement op- * During the replacement operation, TEST RUN is displayed on the remote controller eration must be performed before performing a test run. and LED1 and LED2 on the control board of the outdoor unit flash together.
Page 12
Please be sure to put the contact address/telephone number on this manual before handing it to the customer. HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN Printed in Japan BG79U130H01...