Application Data - Payne PY3G Series Product Data

13 seer single packaged air conditioner and gas furnace system with r-410a refrigerant single and three phase 2-5 nominal tons (sizes 024-060)
Hide thumbs Also See for PY3G Series:
Table of Contents

Advertisement

APPLICATION DATA

Condensate trap — A 2- -in. (51 mm) condensate trap must be
field supplied.
Ductwork — Secure downflow discharge ductwork to roof curb.
For horizontal discharge applications, attach ductwork to unit with
flanges.
To convert a unit to downflow discharge — Units are equipped
with factory- -installed inserts in the down- -flow openings. Removal
of the inserts is similar to removing an electrical knock- -out. Use
the duct cover to seal the horizontal discharge openings in the unit.
Units installed in horizontal discharge orientation do not require
duct covers.
Airflow — Units are draw- -thru in the cooling mode and
blow- -thru in the heating mode.
Maximum cooling airflow — To minimize the possibility of
condensate blow- -off from the evaporator, airflow through the units
should not exceed 450 cfm per ton.
Minimum cooling airflow — Minimum cooling airflow is 350
cfm per ton.
Minimum ambient cooling operation temperature — All
standard units have a minimum ambient operating temperature of
40_F (4_C). With accessory low ambient temperature kit, units can
operate at temperatures down to 0_F (- -18_C).
Minimum temperature — Air entering the heat exchanger in
heating mode must be a minimum of 50_F (10_C) continuous
and/or 45_F (7_C) intermittent.