7. Pack the insulation removed in step 4 around the pipe to prevent air flowing through the tube either into
or out of the firebox.
8. Be sure the gas is turned off at the appliance, then turn the gas on at the cut off valve and test the gas
line connections for leaks with soapy water solution or a liquid leak detector. DO NOT USE A MATCH
OR OTHER FLAME SOURCE TO CHECK FOR GAS LEAKS. If a gas leak is detected, turn the gas off
immediately and fix the leak.
9. Proceed with testing the appliance for leaks and adjusting it as required by the manufacturer
instructions.
F
25
iguRe
OUTER FIREPLACE WRAP
INNER FIREPLACE
WRAP
SIDE BRICK
26" MAX.
FIREPLACE FIREBOX
HEARTH BRICK
GAS LINE ACCESS TUBE
a
d
pplying
ecoRative
Do not allow the trim materials to extend closer than 3/8 inch to the vertical edges of the firebox opening if you
plan to equip the fireplace with glass doors.
The face of your fireplace may be left exposed or trimmed with any noncombustible material such as brick,
stone or marble. If a trim is installed, be sure it is fastened snugly to the face of the fireplace. A crack between
the material and the face of the fireplace could pose a fire hazard and impair the proper operation of the
fireplace. Blocking the fireplace with framing and attaching the base to the supporting floor will further reduce
the possibility of such a crack developing.
Wall ties should be fastened to the face of the fireplace with sheet metal screws and placed in the mortar joints
of masonry trim.
Combustible material must not be installed below the top spacers of the fireplace or overlap the sides of the
fireplace face. Seal the face of the fireplace to the surrounding wall with non-combustible caulk or trim materials
to prevent cold air leakage around the fireplace.
The trim should not block or restrict in any way the flow of air into the side air inlets in the face of the
fireplace.
Be sure to provide the required floor protection as described in a preceding section of this manual.
Combustible mantles and trim must be installed in accordance with the National Fire Protection Association
- ANSI NFPA 211 Standard - Section 7-2.3.3.
24
i
nstallation
MAINTAIN 1/2" MINIMUM
AIR SPACE CLEARANCE TO
COMBUSTIBLES FOR GAS
LINE OUT TO 4" FROM SIDE
OF THE FIREPLACE
COMBUSTIBLE MATERIALS MAY BE
LOCATED AT ZERO CLEARANCE TO GAS
LINE BEYOND 4" FROM FIREPLACE SIDE
REPACK INSULATION
AROUND GAS LINE
WHERE IT PASSES THRU
GAS LINE TUBE FOR
PROPER SEAL
t
F
RiM to the
iReplace
BACK RE-
FRACTORY
BRICK
KNOCKOUT
SIDE RE-
FRACTORY
BRICK
53D9028