Product Specifications - AMX NXA-UPS1500 Operation/Reference Manual

Amx uninterruptible power supply operation/reference guide
Hide thumbs Also See for NXA-UPS1500:
Table of Contents

Advertisement

NXA-UPS1500 Uninterruptible Power Supply

Product Specifications

NXA-UPS1500 Product Specifications
Input:
Output:
Battery:
LED indicators:
Display LCD:
Communication:
Overload
Protection:
Short Circuit
Protection:
2
• Voltage Window (DIP Switch selectable):
120V: 110/115/120 Vac
+35% ˜ -32%
• Inrush Current:
120V: <40A
• Frequency: 45 ˜ 65Hz (50/60Hz auto-sensing)
• Voltage Window (AC Mode):
120V: 110/115/120 Vac
+8% ˜ -12%
• Voltage Window (INV Mode):
120V: 110/115/120 Vac +/-5%
• Max Output Current:
120V: 14A (continuous)
• Type: 12V, sealed lead acid maintenance-free
• Capacity: 9AH
• Quantity: 4 12V batteries required
• Capacity (VA/W):1500/900
• Wave Form: Pure sine wave
• Frequency: 50Hz/60Hz +/-0.1Hz
• Transfer Time:2 ms typical
• Autonomy: > 8 min.
• DC Start: Yes
• Voltage:
120V: 24 Vdc
• Recharge Time: 2 ˜ 4 hours to 90%
• Storage:
At -15 to +30°C (+5 to +86°F)
Charge every 6 months
• Utility mode
• Backup mode
• Battery conditions
• Load level (%)
• Battery level (%)
• Bypass
• AVR-Boost/AVR Buck
RS-232
AC Mode: >110% Buzzer
continuously alarms, and shuts down in
10 minutes.
AC Mode: Breaker and
electronic circuit
• Max short circuit output current:
120V: 50A, 8 cycles (Inverter Mode
short circuit current limitation)
240V: 220/230/240 Vac
+35% ˜ -32%
240V: <20A
240V: 220/230/240 Vac
+8% ˜ -12%
240V: 220/230/240 Vac +/-5%
240V: 7A (continuous)
240V: 48 Vdc
At +30 to +45°C (+86 to +113°F)
Charge every 3 months.
• Battery Low/Replace/Fault
• UPS Fault
• Site Wiring Fault
• Overload
Inverter Mode: >120% Buzzer
continuously alarms, and shuts down in 10
seconds.
Inverter Mode: Shut down
automatically in 8 cycles
240V: 25A, 8 cycles (Inverter Mode short
circuit current limitation)
NXA-UPS1500 Uninterruptible Power Supply

Advertisement

Table of Contents
loading

Table of Contents