Download Print this page
AMX Voltage Output/Analog Input Card NXC-VAI4 Installation Manual

AMX Voltage Output/Analog Input Card NXC-VAI4 Installation Manual

Voltage output/analog input card, control cards and netmodules
Hide thumbs Also See for Voltage Output/Analog Input Card NXC-VAI4:

Advertisement

Quick Links

NetLinx Control Cards and NetModules
NetLinx Control Cards can be installed in either the NXF CardFrame, NI-4000, or
NetModules. This document provides basic specifications and wiring information for
the NetLinx Control cards. For detailed information on the cards, refer to the NetLinx
CardFrame, Control Cards, and NetModules Instruction Manual available on-line via
www.amx.com.
NXC-VAI4 Analog Voltage Control Card
The NXC-VAI4 Analog Voltage Control Card (FG2025) provides 4 independent
analog-to-digital inputs and four independent digital-to-analog outputs, which are
controllable over the ICSP network. Each port can be configured for a variety of DC
input and output signals. The NXC-VAI4 incorporates the functionality of the AXC-VAI2
and AXC-VRG AXlink cards.
NXC-VAI4 Specifications
Power Requirements:
330 mA @ 12 VDC
Inputs:
Four high-impedance analog DC inputs.
Outputs:
Four analog DC outputs (user-configurable).
D/A, A/D conversion:
0-bit A/D and D/A converters for analog sampling and
control.
Available input voltages:
0 V to +12 V.
Available output voltages:
-12 V to +12 V:
The output voltage may be software-configured for any min
and max levels between -12 and +12 VDC.
• Maximum output current = 60 mA per output.
• Over-voltage protection to +28 VDC.
External reference:
A user supplied external reference voltage can be used to
set the maximum voltage range for the D/A outputs. The full
analog output range is scaled to fit the maximum range set
by the external reference.
Output voltage may be set to any level between 0-12 VDC,
referenced to the external reference voltage input and the
NXC-VAI4 power supply GND.
External reference input:
Maximum external reference input voltage = +12VDC.
(EREF, 1 for each output)
Over-voltage protection to +28 VDC.
Internal reference output:
+5 V reference output, maximum current = 60 mA.
(IREF)
This output is intended to drive a ground-referenced load.
I/O Status LEDs 1-8:
LEDs light to indicate ON status.
(two LEDs per channel)
4 yellow LED's (one per channel) light to indicate input signal
changes reported to the Master.
4 red LED's (one per channel) light to indicate output signal
changes. Output LEDs blink to indicate that the power-up or
limit levels have not been set.
• LED 1: Output #1 (red)
• LED 2: Input #1 (yellow)
• LED 3: Output #2 (red)
• LED 4: Input #2 (yellow)
• LED 5: Output #3 (red)
• LED 6: Input #3 (yellow)
• LED 7: Output #4 (red)
• LED 8: Input #4 (yellow)
Wiring:
Captive-wire connectors.
Device ID:
0x010D
Firmware ID:
• 0x0113 (Download)
• 0x0114 (Boot)

Pinouts and Functions:

NXC-VAI4 Pinouts, Signals, and Functions
Pin Function
Pin Function
1
Output #1 (GND)
9
Input #1 (GND)
2
Output #1
10
Input #1
3
Output #2 (GND)
11
Input #2 (GND)
4
Output #2
12
Input #2
5
Output #3 (GND)
13
Input #3 (GND)
6
Output #3
14
Input #3
7
Output #4 (GND)
15
Input #4 (GND)
8
Output #4
16
Input #4

Channel Assignments:

Off = 50% voltage, and all channel assignments are mutually exclusive.
Note: PU, PN and PX must be set for all eight levels before using the card.
NXC-VAI4
Pin Function
17
+5 V Reference output (GND)
18
+5 V Reference output
19
External Reference input (GND)
20
External Reference input
Voltage Output/Analog Input Card
NXC-VAI4 Channel Assignments
Channel
State Function
Channel 1
ON
While channel 1 is ON, the voltage on Output 1 will ramp up at the
"CURRENT OUTPUT 1 RAMP UP TIME" rate. The voltage ramp
stops if the maximum is reached.
OFF
Stops voltage ramping on Output 1 at current value.
Channel 2
ON
While channel 2 is ON the voltage on Output 2 will ramp up at the
"CURRENT OUTPUT 2 RAMP UP TIME" rate. The voltage ramp
stops if the maximum is reached.
OFF
Stops voltage ramping on Output 2 at current value.
Channel 3
ON
While channel 3 is ON the voltage on Output 3 will ramp up at the
"CURRENT OUTPUT 3 RAMP UP TIME" rate. The voltage ramp
stops if the maximum is reached.
OFF
Stops voltage ramping on Output 3 at current value.
Channel 4
ON
While channel 4 is ON the voltage on Output 4 will ramp up at the
"CURRENT OUTPUT 4 RAMP UP TIME" rate. The voltage ramp
stops if the maximum is reached.
OFF
Stops voltage ramping on Output 4 at current value.
Channel 5
ON
While channel 5 is ON the voltage on Output 1 will ramp down at the
"CURRENT OUTPUT 1 RAMP DOWN TIME" rate. The voltage
ramp stops if the minimum is reached.
OFF
Stops voltage ramping on Output 1 at current value.
Channel 6
ON
While channel 6 is ON the voltage on Output 2 will ramp down at the
"CURRENT OUTPUT 2 RAMP DOWN TIME" rate. The voltage
ramp stops if the minimum is reached.
OFF
Stops voltage ramping on Output 2 at current value.
Channel 7
ON
While channel 7 is ON the voltage on Output 3 will ramp down at the
"CURRENT OUTPUT 3 RAMP DOWN TIME" rate. The voltage
ramp stops if the minimum is reached.
OFF
Stops voltage ramping on Output 3 at current value.
Channel 8
ON
While channel 8 is ON the voltage on Output 4 will ramp down at the
"CURRENT OUTPUT 4 RAMP DOWN TIME" rate. The voltage
ramp stops if the minimum is reached.
OFF
Stops voltage ramping on Output 4 at current value.
Channel 9
ON
Reserved [do not use].
OFF
Reserved [do not use].
Channel 10
ON
While channel 10 is ON the voltage on Output 1 is set to 100%.
OFF
Sets Output 1 voltage to 50%.
Channel 11
ON
While channel 11 is ON, the voltage on Output 2 is set to 100%.
OFF
Sets Output 2 voltage to 50%.
Channel 12
ON
While channel 12 is ON, the voltage on Output 3 is set to 100%.
OFF
Sets Output 3 voltage to 50%.
Channel 13
ON
While channel 13 is ON, the voltage on Output 4 is set to 100%.
OFF
Sets Output 4 voltage to 50%.
Channel 14
ON
While channel 14 is ON, the voltage on Output 1 is set to 0%.
OFF
Sets Output 1 voltage to 50%.
Channel 15
ON
While channel 15 is ON, the voltage on Output 2 is set to 0%.
OFF
Sets Output 2 voltage to 50%.
Channel 16
ON
While channel 16 is ON, the voltage on Output 3 is set to 0%.
OFF
Sets Output 3 voltage to 50%.
Channel 17
ON
While channel 17 is ON, the voltage on Output 4 is set to 0%.
OFF
Sets Output 4 voltage to 50%.
Channel 18
ON
While channel 18 is ON, the voltage on Output 1 is set to 75%.
OFF
Sets Output 1 voltage to 50%.
Channel 19
ON
While channel 19 is ON, the voltage on Output 2 is set to 75%.
OFF
Sets Output 2 voltage to 50%.
Channel 20
ON
While channel 20 is ON, the voltage on Output 3 is set to 75%.
OFF
Sets Output 3 voltage to 50%.
Channel 21
ON
While channel 21 is ON, the voltage on Output 4 is set to 75%.
OFF
Sets Output 4 voltage to 50%.
Channel 22
ON
While channel 22 is ON, the voltage on Output 1 is set to 25%.
OFF
Sets Output 1 voltage to 50%.
Channel 23
ON
While channel 23 is ON, the voltage on Output 2 is set to 25%
OFF
Sets Output 2 voltage to 50%.
Channel 24
ON
While channel 24 is ON, the voltage on Output 3 is set to 25%
OFF
Sets Output 3 voltage to 50%.
Channel 25
ON
While channel 25 is ON, the voltage on Output 4 is set to 25%
OFF
Sets Output 4 voltage to 50%.
Installation Guide

Advertisement

loading

Summary of Contents for AMX Voltage Output/Analog Input Card NXC-VAI4

  • Page 1: Pinouts And Functions

    NetLinx Control cards. For detailed information on the cards, refer to the NetLinx CardFrame, Control Cards, and NetModules Instruction Manual available on-line via www.amx.com. NXC-VAI4 Analog Voltage Control Card The NXC-VAI4 Analog Voltage Control Card (FG2025) provides 4 independent analog-to-digital inputs and four independent digital-to-analog outputs, which are controllable over the ICSP network.
  • Page 2: Programming Information

    ©2007 AMX. All rights reserved. AMX and the AMX logo are registered trademarks of AMX. AMX reserves the right to alter specifications without notice at any time. 3000 RESEARCH DRIVE, RICHARDSON, TX 75082 • 800.222.0193 • fax 469.624.7153 • technical support 800.932.6993 • www.amx.com NXC-VAI4 SEND_COMMANDs (Cont.) DEFAULT ALL Sets all card settings back to their original factory settings.

This manual is also suitable for:

Netlinx nxc-vai4