How To Install The Outdoor Unit; Transporting; Installing The Outdoor Unit - Sanyo R410A Installation Instructions Manual

W-3way eco-i system air conditioner
Hide thumbs Also See for R410A:
Table of Contents

Advertisement

3. HOW TO INSTALL THE OUTDOOR UNIT

3-1. Transporting

When transporting the unit, have it delivered as close to the installation site as
possible without unpacking. Use a hook for suspending the unit. (Fig. 3-1)
CAUTION
● When hoisting the outdoor unit, pass ropes or straps under the bottom plate
as shown in the figure at right. When hoisting, the angle between the rope
and top panel must be 70° or greater so that the rope does not come into
contact with the fan guard.
(Use 2 lengths of rope 25 ft. long or longer.)
● When passing the ropes through the square holes of the bottom plate:
Place the rope in the outer edge of the square holes.
● Use protective panels or padding at all locations where the rope contacts the
outer casing or other parts to prevent scratching. In particular, use protective
material (such as cloth or cardboard) to prevent the edges of the top panel
from being scratched.
● Be careful of the fan.
There is danger of injury if the fan starts to turn during inspection. Be sure to
turn OFF the remote power switch before beginning inspection.

3-2. Installing the Outdoor Unit

(1) Use anchor bolts (M12 or 15/32") or similar to securely anchor the unit in
place. (Fig. 3-2)
(2) Be sure the rubber vibration insulator and platform extend to the inside of the
legs. In addition, the washers used to anchor the unit from the top must be
larger than the installation anchor holes. (Figs. 3-2 and 3-3)
(Positions where anchor bolts are fastened)
Installation anchor hole (4-19/32
31-1/8
(Installation hole pitch)
35
(Ceiling panel dimensions)
113 (Ceiling panel dimensions)
35
(Ceiling panel dimensions)
(Ceiling panel dimensions)
3
31-1/8
(Installation hole pitch)
109 (Installation hole pitch)
25/32 oval holes)
35
(Ceiling panel dimensions)
31-1/8
(Installation hole pitch)
(Installation hole pitch)
Top view
Fig. 3-4
unit: in.
35
31-1/8
24
Fig. 3-1
Plate leg
Anchor bolts
Washer
(3-15/16)
The vibration insulator, base, or platform must
be large enough to bear the full surface of the
base plate legs.
Fig. 3-2
(Detailed view of legs)
4 – 19/32
25/32 hole
Fig. 3-3
Vibration insulator
1-31/32
Base
Unit: in.
Unit: in.
1-33/64

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents